SECTION 9: PPC Series 50/60 Hz Variable Frequency Drives
STEP 7
Motor Horsepower Screen
Enter the motor horsepower (HP) from the motor
nameplate. Scroll to select the horsepower and press
SAVE. The sample here shows 3.0 HP.
PAR EDIT
REM
9909 MOTOR NOM POWER
3.0 hp
EXIT
STEP 8
For Submersible Pumps Only
Enter the minimum speed allowed by the motor vendor
(consult motor literature). This is to prevent motor
bearing damage.
PAR EDIT
REM
2001
MIN SPEED
0 RPM
EXIT
STEP 9
Scroll To Select Constant Pressure Point 
Example shows 40 PSI.
REM
PAR EDIT
4011 INTERNAL SET PNT
40 PSI
EXIT
74
00:00
SAVE
00:00
SAVE
00:00
SAVE
STEP 10
Transducer 100% Value
Enter the transducer's full range value which should
be stated on the transducer body. Scroll to select the
pressure and then press SAVE. The sample here shows
100 PSI.
PAR EDIT
REM
4009 100% VALUE
100.0 PSI
EXIT
NOTICE: DO NOT choose maximum pressure.
range: 0... 10 bar / 145 psi
max. pressure: 25 bar / 362.5 psi
UE: 80...330 VDC
OUT: 4...20mA Load <(N-8V) /0.02A
STEP 11
PID Sleep Level Screen
Enter the PID sleep level. This is a motor speed setting.
If the motor speed falls below this RPM, the PID sleep
function will be enabled. This is a Drive-assigned value.
For additional information, refer to the PPC5 Users
Manual. Scroll to select the speed and then press SAVE.
The sample here shows 3000 RPM.
Burn Hazard. If the sleep level is set too
low, the pump my run without flow. This can boil water
inside the pump, causing dangerously high pressure
and temperature.
PAR EDIT
REM
4023 PID SLEEP LEVEL
3000 rpm
00:00
EXIT
00:00
SAVE
Use this Full Range Value
Do NOT use Maximum Pressure
SAVE