SECTION 8: Pentek Intellidrive

8.2 Description

Specifications/Ratings
Input Voltage ...................... 1-Phase 230VAC Nominal (190–265VAC)
Input Frequency ..................................................................... 50/60Hz
Ambient Temperate Range .................... -4 to 122 °F (-20° to 50 °C)
Output Connections .........................3-Phase, 3-Wire/1-Phase or
Max Motor Cable Length .................................................... 1,000 feet
Enclosure ........................................................................................ 3R
Table 1 - Specifications
HP
Model
Motor Type
Range
2-WIRE* 1-PHASE
PID10
3-WIRE* 1-PHASE
0.5–1 HP
3-PHASE
2-WIRE* 1-PHASE 0.5–1.5 HP
PID20
3-WIRE* 1-PHASE
0.5–2 HP
3-PHASE
3-PHASE
0.5–5 HP
PID50
2-WIRE
0.5 - 1.5
3-WIRE
0.5-2
The Pentek Intellidrive is specifically designed to
operate 4" submersible pumps and 3-phase above
ground pumps in water well and residential booster
applications. Each Drive is rated for maximum output
amp rating. Any use of Drive outside of intended
design parameters will void warranty. If Drive is used
Figure 1 - A typical residential installation layout
Gnd
(3 phase only)
48
1-Phase/2-Wire
Maximum
Input
Enclosure
Output
Voltage
Type
AMPS
9.5A
7.5A
5A
11A
190V –
NEMA 3R
13.5A
265V
outdoor
8.5A
18A
11A
13.5A
* Select drives by S.F. amps of pump motor.
PENTEK
INTELLIDRIVE™
Gnd
Variable Frequency Drives
with above ground motors not rated for a Variable
Frequency Drive, maximize motor life by limiting lead
length to 25 ft. Refer to pump Owner's Manual and the
National Electrical Code for proper wire size.
Each carton contains:
• Pentek Intellidrive Variable Frequency Drive
• Pressure Transducer
• 10' Pressure Transducer Cable
• Quick Start Guide
PIDXX
Product Family
PID - PENTEK INTELLIDRIVE
HP Range
10 = up to 1.0 HP
20 = up to 2.0 HP
50 = up to 5.0 HP
The PID10 will operate a 1-Phase 2-Wire, 1-Phase
3-Wire, and 3-Phase motor up to 1HP.
The PID20 will operate a 1-Phase 2-Wire up to 1.5HP
and a 1-Phase 3-Wire or 3-Phase motor up to 2HP.
The PID50 will operate a 1-Phase 2-Wire up to 1.5HP,
1-Phase 3-Wire up to 2HP, or 3-Phase motor up to 5HP.
Transducer; install in straight
pipe downstream of tank, at
least one foot away from
pipe fittings on each side.
6004 0509