Internal Diagnostics; Led Explanation - Parker Sporlan PSK Series Manual

Refrigeration controllers
Table of Contents

Advertisement

Page 2 – Bulletin 100-50-6.1
3
SETTINGS
3.1 Setting the working setpoint
• make sure no procedure is running
• press
: LED
will flash
• press
or
within 15 seconds; also look at parameters r1, r2 and r3
• press
or do not press any key for 15 seconds.
You also can modify the working setpoint through parameter SP.
3.2 Setting configuration parameters
To gain access to the procedure:
• make sure no procedure is running
• press and hold
and
for 4 seconds: the display will show "PA"
• press
• press
or
within 15 seconds to set display to "-19"
• press
or do not press any key for 15 seconds
• press and hold
and
for 4 seconds: the display will show "SP".
To select a parameter:
• press
or
To modify a parameter:
• press
• press
or
within 15 seconds
• press
or do not press any key for 15 seconds.
To quit the procedure:
• press and hold
and
60 seconds.
Switch off/on the power supply of the controller after the
modification of the parameters.
3.3 Restoring the default value of configuration parameters
• make sure no procedure is running
• press and hold
and
for 4 seconds: the display will show "PA"
• press
• press
or
within 15 seconds to set the display to "743"
• press
or do not press any key for 15 seconds
• press and hold
and
for 4 seconds: the display will show "dEF"
• press
• press
or
within 15 seconds to set the display to "149"
• press
or do not press any key for 15 seconds: the display will
show "dEF" flashing 4 seconds, after which the controller will quit
the procedure
• switch off/on power to the controller.
Make sure the default value of the parameters is correct, in
particular note if the probes are PTC probes.
4
SIGNALS
4.1 Signals

LED EXPLANATION

LED compressor
if lit, the compressor will be turned on
if flashing:
• the modified working setpoint will be running
• a compressor protection will be running (parameters C0
and C2; the compressor delay since the end of the cabinet
probe error is 2 minutes)
for 4 seconds or do not press any key for
LED defrost
if lit, the defrost will be running
LED alarm
if lit, an alarm will be running
°C °C LED
if lit, temperature measurements will be in degrees
Celsius (parameter P2)
°F
°F LED
if lit, temperature measurements will be in degrees
Fahrenheit (parameter P2)
5

INTERNAL DIAGNOSTICS

5.1 Internal diagnostics
CODE EXPLANATION
Pr1 Cabinet probe error
Solution:
• look at parameter P0
• check the integrity of the probe
• check the connection between controller and probe
• check the cabinet temperature
Effects:
• the compressor will be turned on
When the conditions that triggered the alarm are no longer present, the
controller will return to normal operation.
6
TECHNICAL DATA
6.1 Technical data
Frontal bezel protection: IP 65.
Connections (use copper conductors only): screw terminal blocks
(power supply, input and output).
Working temperature: from 0 to 55°C (32 to 131°F), 10 to 90%
relative humidity (without condensation).
Power supply: 115 VAC/230 VAC, 50/60 Hz, 3 VA (approximate).
Insulation class: 2.
Measure inputs: 1 (cabinet probe) for PTC/NTC probes.
Working range: from -50.0 to 150.0°C (-50 to 300°F) for PTC probe,
from -40.0 to 105.0°C (-40 to 220°F) for NTC probe.
Resolution: 0.1°C/1°C/1°F.
Digital outputs: 1 relay:
• c ompressor relay: 16 res. A @ 250 VAC (change-
over contact); 5 FLA, 30 LRA.
The maximum current allowed on the load is 10 A.