General Location
Please note the following criteria when choosing a location for the inverter:
Selection
Only install on a solid, non-flammable surface
Max. ambient temperatures: -40 °F/+140 °F (-40 °C/+60 °C)
Relative humidity: 0–100%
The air flow direction within the inverter is from right to top (cold air intake on the right, hot
air outflow at the top). The waste air may reach a temperature of up to 70 °C.
Do not install the inverter with the connections upwards on a vertical wall
or column.
Do not install the inverter overhanging with the connections upwards.
Do not install the inverter overhanging with the connections downwards.
Do not install the inverter on the ceiling.
9