Fault Shutdowns
Code
Description
Check
A check engine
engine
fault occurs when
(fault) [
the ECM sends a
signal for the
generator set
controller to shut
down because the
engine has stalled
ECM voltage
No or low voltage
(fault) ]
to the ECM
[ Note: Available on software version 1.3.0 or higher. On software version 1.2.0 and below, this condition was displayed as Out of fuel.
] Note: Available on software version 1.3.0 or higher. On software version 1.2.0 and below, this condition was displayed as Low battery fault.
Figure 2-6 Advanced Digital Control II Fault Shutdown
Warnings
Code
Description
High battery
High battery
voltage warning.
Fault condition
clears when the
battery voltage
returns to a
voltage within the
limits.
Low battery
Low battery
voltage warning.
Fault condition
clears when the
battery voltage
returns to a
voltage within the
limits.
Weak
Low cranking
battery
battery
Hi CO:
High CO from
engine
ECM. Fault code
is displayed if the
presence of CO is
detected because
of the
time-weighted
average presence
of CO. Activates
the CO cabin
alarms.
20
Section 2 Operation
Sensing
Active
Mechanism
State
ECM
N/A
ECM
N/A
Sensing
Active
Mechanism
State
Analog input
Above setting
Analog input
Below setting
Analog input
Below setting
ECM data
Control limit
Inhibit
Delay
Default
Time
Time
Setting Check
N/A
N/A
N/A
N/A
N/A
N/A
Inhibit
Delay
Default
Time
Time
Setting Check
0 sec
10 sec
16 volts
for 12 volt
system
0 sec
10 sec
12.6 volts
for 12 volt
system
0 sec
2 sec
9 VDC
during
cranking
0 sec
5 sec
N/A
Check for high fuel restrictions.
Check for air leaks in the supply side
of the fuel system.
Check for an inoperative low or high
pressure fuel pump.
check for fuel vaporization in higher
than maximum temperature operation
specifications.
Contact an authorized
distributor/dealer for service if
problem continues.
Check if the 10 amp, F1 fuse is blown
or missing.
Check if lead 70 circuit is open
between plug, P1--4 and the battery
during cranking attempts.
Check for low voltage on lead 70.
Contact an authorized
distributor/dealer for service if
problem continues.
Check the battery rating and
condition.
Check the battery rating and
condition.
Charge or replace the battery.
Check the battery rating and
condition.
Charge or replace the battery.
Ensure windows are open for proper
ventilation.
Operate the blower to expel
dangerous fumes.
Move the vessel away from other
vessels (as another vessel may be the
source for the presence of the CO).
Check the generator exhaust system
(see Section 3.6).
Contact an authorized
distributor/dealer for service.