Flue Options; Cabinet Mounted Balanced Horizontal Flue Options; Plume Management - Bosch Worcester Greenstar Danesmoor External Regular ErP+ 12/18 Installation, Commissioning And Servicing Instruction Manual

Floor standing oil-fired condensing boiler using room sealed flue for fully pumped open vent or sealed central heating systems and domestic hot water cylinders
Hide thumbs Also See for Worcester Greenstar Danesmoor External Regular ErP+ 12/18:
Table of Contents

Advertisement

Pre-Installation
4.9

Flue options

4.9.1

Cabinet mounted balanced horizontal flue options

It is strongly recommended that the flue terminal faces
away from walls to minimise the occurrence of wetting.
• The horizontal flue is fitted to the rear or either side of the cabinet.
REAR FLUE OUTLET
LEFT HAND FLUE OUTLET
RIGHT HAND FLUE OUTLET
Fig. 21 Flue options
4.9.2

Plume management

NOTICE: Flue length:
▶ The flue length of all the external boilers using this
plume management application will be in the range
of 160 to 5000mm.
Effective lengths of elbows
Bend
Flue
90°
1000mm
45°
500mm
Table 6 Effective lengths of bends
Fitting the terminal plume management kit
1. Remove and retain the screws that secure the terminal end into the
flue.
2. Discard the terminal end.
3. Fit the terminal elbow into the flue but do not secure with the screws
until the plume management system has been assembled.
18
Plan
Fig. 22 Fitting the terminal bend
View
1. Connect the sections of the plume management for desired length.
FRONT
2. Once the plume management system is in place and secured to the
▶ The terminal end can be positioned up to 45° either side of the
▶ Adjust the plume management terminal end into the desired position
Plan
View
FRONT
Plan
View
FRONT
Plume
1000mm
500mm
Fig. 23 Plume management detail
Greenstar Danesmoor External
1.
– Screw the clamp into the wall.
– Push the extension/s tube fully into the 90° bend, then withdraw
the tube by approximately 10mm to allow for expansion.
wall, secure the terminal bend with the screws remove earlier.
central position, for plume re-direction.
and secure with the screws provided.
±45°
Min. 150mm
2.
ErP+
and External System
1.
3.
2.
6720645523-50.1Wo
1.
M
6720645523-51.1Wo
ErP+
6720821725 (2018/04)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Worcester greenstar danesmoor external regular erp+ 18/25Worcester greenstar danesmoor external system erp+ 18/25Worcester greenstar danesmoor external system erp+ 25/32Worcester greenstar danesmoor external regular erp+ 25/32

Table of Contents