Fig. 39 Refitting the control panel
5.9

Electrical

CAUTION: ISOLATE THE 230v ELECTRICITY SUPPLY
▶ Ensure that the electricity supply is safely Isolated
and secured to prevent inadvertent re-connection.
Information on safe isolation can be found in the
Health and Safety Executive guidance HSG85. Using
test equipment approved to GS38 confirm that the
electricity supply is disconnected.
▶ The mains electrical supply to the boiler and system
wiring centre must be common and through either a
common fused double pole isolator or a fused three
pin plug and unswitched socket.
▶ The isolator shall be sited next to the boiler for new
systems and where practicable, replacement boilers.
▶ The isolator must have a contact separation of 3mm
minimum between all poles.
▶ Any additional components that are connected to the
boiler with mains electrical supply must not have a
separate supply.
▶ External 5 Amps.
▶ When stripping wires ensure copper strands do not
fall into the control box.
Access to 230V connections
▶ Remove the four cover panel retaining screws [2] from the control
box [1].
▶ Release screws [4] from cable clamp [7].
▶ Pull inner clamp part [6] outwards.
▶ Feed sufficient power cable [5] through the cable clamp [7] and
secure grip with screws [4].
▶ Separate wires from cable end and strip to 6mm.
230V connections
▶ Connect LIVE wire (Brown) to terminal L.
▶ Connect NEUTRAL wire (Blue) to terminal N.
▶ Connect EARTH wire (Green/Yellow) to the earth terminal
Electrical power cable
▶ Route the power cable down the side panel using the
clip provided on the support panel to the external
connection point avoiding any potentially hot
surfaces allowing sufficient cable to pivot the control
box into the service position.
Greenstar Danesmoor External
ErP+
and External System
F
E
ErP+
6720821725 (2018/04)
2
1
4
6
5
Fig. 40 Electrical connections
A frost thermostat is fitted as standard to the external
appliance to provide frost protection.
Installation
3
2
5
7
230V
6720809437-21.1Wo
25