Commissioning
1
6
Fig. 55
[1]
Reset button
[2]
Combustion head
[3]
Pressure adjustment
[4]
Bleed and pressure gauge port
[5]
Air shutter display window
[6]
Air shutter adjuster
Combustion settings
APPLIANCE MUST BE SET TO CO
AIR SETTINGS GIVEN ARE APPROXIMATE ONLY, AS FLUE LENGTH AND NOZZLE VARIATIONS WILL AFFECT THIS.
Nominal boiler rating at normal operating temperature using Kerosene (Class C2)
Oil pump
Fuel flow
pressure
rate
Nozzle
bar
psi Kg/h
Greenstar Danesmoor 12/18 model
0.40 x 80° EH
8.5 123 1.12 1.38
0.40 x 80° EH
10.0 145 1.30 1.60
0.50 x 80° EH
10.0 145 1.54 1.90
Greenstar Danesmoor 18/25 model
0.50 x 80° EH
10.0 145 1.54 1.90
0.60 x 60° EH
8.8 128 1.84 2.28
0.65 x 80° EH
9.5 138 2.15 2.66
Greenstar Danesmoor 25/32 model
0.65 x 80° EH
9.8 142 2.15 2.66
0.75 x 80° EH
10.3 150 2.46 3.04
0.85 x 80° EH
10.0 145 2.78 3.44
Table 9 Combustion settings
32
2
3
4
5
6720809437-34.1Wo
LEVELS.
2
Approx
flue gas
Combustion
temp.
head settings
l/h
°C
%CO2
mm
67
12.0
10.5
70
11.5
11
80
12.0
11.5
76
12.5
12.5
81
12.5
14
90
12.5
15
79
11.5
19
84
12.0
19
85
12.5
19
6.4.7

Central heating

▶ Open all radiator valves.
▶ Set room thermostat to maximum.
▶ Set programmer to ON for CH, OFF for DHW (if applicable).
▶ Turn the thermostat control [1] to max.
The demand indicator [2] should illuminate and the burner should be ON
with the circulating pump.
▶ Ensure all radiators are heating up evenly and balance the system to
the temperature difference required for the heating flow and return
according to the heating load.
▶ Set the room thermostat to minimum.
The demand indicator light [3], burner and circulating pump should
be off.
▶ Check that any other controls that are fitted to the system are
operating properly.
1
Fig. 56
Approx.
air
Input
Output
setting
(appliance)
(appliance)
kW
kW
2.3
13.2
13.0
1.75
15.3
15
2.5
18.3
18.0
1.5
18.3
18.0
3.25
21.9
21.5
3.25
25.5
25.0
3.5
25.5
25.0
4.25
29.1
28.5
4.75
32.7
32.0
Greenstar Danesmoor External
ErP+
2
3
6720809437-28.1Wo
Air damper
Flue
disc
damper
setting
required
Burner head
A
Yes
BX & recirculation tube
B
Yes
BX & recirculation tube
C
Yes
BX & recirculation tube
N/A
Yes
BX
N/A
Yes
BX
N/A
Yes
BX
N/A
No
BX
N/A
No
BX
N/A
Yes
BX
and External System
ErP+
6720821725 (2018/04)