Controller replacement
AK-CC 750 on AK-SM 800
ADAP-KOOL® Refrigeration Control System

Advertisement

loading

Summary of Contents for Danfoss ADAP-KOOL AK-CC 750

  • Page 1 Service Guide Controller replacement AK-CC 750 on AK-SM 800 ADAP-KOOL® Refrigeration Control System...
  • Page 2 . 8. Set # of evaporators to appropriate value. At AK-SM 800: 1. Login to controller 2. Press menu button on keypad and select option 2 for ‘Network Nodes’ . 2 | AX278947943210en-000101 © Danfoss | ADAP-KOOL® | 2018.08...
  • Page 3 To do so, from current screen go to Config Status tab, locate case controller address in list and verify status column shows ‘online’ . 6. To download setpoints to controller, press gear button on keypad to enter configuration menu. AX278947943210en-000101 | 3 © Danfoss | ADAP-KOOL® | 2018.08...
  • Page 4 ‘press to deselect all’ . Next, highlight the case controller to download to, and press OK. This should place a check mark in the box next to the controller address. 4 | AX278947943210en-000101 © Danfoss | ADAP-KOOL® | 2018.08...
  • Page 5 11. Return to Setup tab. Ensure drop-down on right is still set to ‘Select Application. Change Configuration Lock to ‘Locked’ and Main Switch to ‘On’ for case operation to begin. AX278947943210en-000101 | 5 © Danfoss | ADAP-KOOL® | 2018.08...
  • Page 6 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.