UNIT DOES NOT FUNCTION
ARE EXTERNAL SUPPLY
STOPS OPEN?
YES
REPEATED DOUBLE FLASH
ON SENSOR?
NO
RECONNECT BATTERY TO SENSOR.
DOES SENSOR FLASH FOR 5 SECONDS?
YES
REPLACE SOLENOID
WATER IS CONTINUOUSLY RUNNING
RECONNECT BATTERY TO SENSOR.
DOES SENSOR FLASH FOR 5 SECONDS?
YES
REPLACE SOLENOID
LOW FLOW ISSUES
ARE EXTERNAL SUPPLY STOPS FULLY
OPEN?
YES
CHECK FOR BLOCKAGE
For toll-free information and answers to your questions, call:
Mon. - Fri. 8:00 a.m. to 8:00 p.m. EST Saturday 10:00 a.m. to 4:00 p.m. EST
IN CANADA 1-800-387-0369 (TORONTO 1-905-306-1093)
Pro duc t name s lis ted herein are trademarks of AS Ameri ca, Inc. ©2 01 8
To learn more about American Standard Selectronic
www.americanstandard-us.com or e-mail us at: CRTTEAM@
TROUBLESHOOTING FLOW CHARTS
HOT LINE FOR HELP
(844) CRT-TEAM / (844) 278-8326
IN MEXICO 01-800-839-1200
Weekdays 8:00 a.m. to 7:00 p.m. EST
Products visit our website at:
®
.com
lixilamericas
NO
OPEN EXTERNAL SUPPLY STOPS.
CRITICALLY LOW BATTERY.
YES
INSTALL NEW BATTERY.
1
1
NO
DEAD BATTERY. INSTALL
NEW BATTERY. REPEAT.
2
2
NO
CHECK FOR DAMAGE TO SENSOR WIRE INSULATION.
REPLACE SENSOR.
CHECK FOR DAMAGE TO SENSOR WIRE INSULATION.
NO
REPLACE SENSOR.
FULLY OPEN EXTERNAL SUPPLY STOPS BY
NO
TURNING COUNTER CLOCKWISE.
INSPECT FILTER ASSEMBLY, AERATOR AND
SOLENOID VALVE. REMOVE, CLEAN AND INSERT
BACK TO ORIGINAL POSITION.
NOTE: AERATOR MUST ONLY BE SERVICED
WITH APPROPRIATE AMERICAN STANDARD
REPAIR PARTS.