First steps in commissioning
Hide thumbs Also See for SIMATIC FM 453:

Advertisement

Connect the programming device to the CPU.
Switch the CPU to the STOP state.
Test: Switch on the power on the power supply module. After a successful internal module test, none
of the three LEDs (INTF, EXTF, STAT) should be lit.
Installing the configuring package on the programming device
The configuring package contains the parameterization tool "Paramerterize FM 453", which contains
functions (FCs), the data structure (UDT 1), a pre-programmed example interface for OP 7/17 (irreve-
lant here) as well as user examples.
Insert the CD ROM in the CD ROM drive of your PG/PC.
Run file Setup.exe on the CD ROM.
Follow the step by step instructions given by the installation program.
The software is installed in the following default directories:
S Parameterization tool "Paramerterize FM 453": "Siemens\Step7\S7FUPOS"
S Function blocks: "Siemens\Step7\S7LIBS\FMSTSV_L"
S Interface for OPs: "Siemens\Step7\EXAMPLES\FM453\zEn17_02_FM453_OP_EX"
S User examples: "Siemens\Step7\EXAMPLES\zEn17_02"
STEP7 project name: "zEn17_02_FM453_EX"
S MD-DBs (startup of stepper motor control): "Siemens\Step7\EXAMPLES\FM453\MD"
The installation of the configuring package is also described in Section 5.1 of the Manual.
Parameterizing the FM 453
If you haven't yet created a project, then proceed as follows:
Create a new project in the SIMATIC Manager create a new project with the commands
File → New
→ Projects
and give it a name. Insert your project in the newly created project window with the com-
mands
Insert → SIMATIC 400 Station.
Select the
SIMATIC 400
Station. Access the S7 hardware configuration with the commands
Edit →
Open
object.
With
Insert → Hardware Components
or
View → Catalog
open the hardware catalog. Within this
catalog select
SIMATIC 400 → RACK-400 → CR2/UR1/UR2
(depending on the rack). Then drag the
rack into your hardware project.
Select, in the same way, the power supply module, the CPU and the FM 453 module with the corres-
ponding reference numbers (MLFBs) in the hardware catalog and drag them into the desired slot (slot
1 for the power supply, slot 3 for the CPU, slot 5 for the FM 453).
Save and compile the created hardware project with the commands
Station → Save and
Compile.
Note: Now, your project contains the configured CPU and FM 453.
Select the FM 453 in your hardware project.
Open the "Properties − FM 453 − (R0/S5)" dialog with
Edit → Object
Properties.
Click on the
Parameters...
button to open the user interface "Parameterize FM 453".
Confirm the message to save the project with OK.