Siemens RUGGEDCOM RS910W Installation Manual page 50

Hide thumbs Also See for RUGGEDCOM RS910W:
Table of Contents

Advertisement

Chapter 6
Certification
EMC Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
40
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Voltage Dips and Interrupts
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Ground
DC Power Ports
± 2 kV Line-to-Ground
AC Power Ports
± 4 kV Line-to-Ground
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
AC Power Ports
100% for 50 Periods
Signal Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
DC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
AC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
Signal Ports
DC Power Ports
DC Power Ports
DC Power Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 2 kV
± 1 kV Line-to-Line
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m Continuous
1000 A/m for 1 s
100% for 5 Periods
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
EMC and Environmental Type Tests
RUGGEDCOM RS910W
Installation Guide
Severity Levels
4
4
x
4
4
4
4
3
4
3
3
3
3
3
3
3
4
4
3

Advertisement