6 Set-up and settings for water

(For media other than water → 7�1: Low flow adjustment)�
► Switch on the supply voltage�
> All LEDs light and go out again step by step� The unit is in the operating mode�
► Let the normal flow circulate in the installation�
► Check the display and determine further actions�
Low
1
0 1 2 3 4 5 6 7 8 9
Low
2
0 1 2 3 4 5 6 7 8 9
Low
3
0 1 2 3 4 5 6 7 8 9
You can restore the factory setting any time� (→ 7�2)�
6.1 High flow adjustment (optional)
The unit determines the existing flow as normal flow and adapts the display repre-
sentation (all LEDs light green)�
Proceed as follows:
► Let the normal flow circulate in the installation�
► Press the pushbutton
> LED 9 lights, after approx� 5 s it flashes�
► Release the pushbutton�
The unit is now adapted to your flow conditions� It passes into the operating mode,
the display should now show example 1�
8
Flow
High
Flow
High
Flow
High
and keep it pressed�
The factory setting is suitable for the applica-
tion�
► No further settings are required�
Your normal flow is below the representation
range of the display�
► Carry out high flow adjustment (→ 6�1)�
Your normal flow exceeds the representation
range of the display (LED 9 flashes)�
► Carry out high flow adjustment (→ 6�1)�