To size wire, the voltage drop of each wire segment must be used and the total
must not exceed 100%.
Example: a 1.5 HP motor, 100' from Service Entrance to Controller (1Ø wire)
and 500' from Controller to Motor (3Ø wire).
• Service Entrance to Controller = 100' of # 10 (100/455) = 22 % (455' from
230V 1Ø chart)
• Controller to Motor = 500' of # 12 (500/709) = 71 % (709' from the 3Ø chart)
• 71% + 22% = 93 %; See Balanced Flow Bulletin or IM182 for more info.