GENERAL DATA - COOLING ONLY (R22)

MODEL

NOMINAL CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT - 1Ø / <3Ø>
POWER SOURCE - 1Ø / <3Ø>
EER - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
AIR DISCHARGE
CONTROL
OPERATION
AIR FLOW
EXTERNAL STATIC PRESSURE (H/M/L)
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLOW
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
UNIT WEIGHT
PIPE CONNECTION
SIZE
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8616 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
INDOOR UNIT
OUTDOOR UNIT
Btu/h
W
W
A
V/Ph/Hz
W/W
HIGH
l/s / CFM
MEDIUM
l/s / CFM
LOW
l/s / CFM
mmAq
dBA
HEIGHT
mm/in
WIDTH
mm/in
DEPTH
mm/in
HEIGHT
mm/in
WIDTH
mm/in
DEPTH
mm/in
kg/lb
mm/in
l/s / CFM
dBA
HEIGHT
mm/in
WIDTH
mm/in
DEPTH
mm/in
HEIGHT
mm/in
WIDTH
mm/in
DEPTH
mm/in
kg/lb
TYPE
LIQUID
mm/in
GAS
mm/in
kg/lb
ACM 40D
ALC 35D
34000
9960
3120
15.2
220 - 240 / 1 / 50 <380 - 415 / 3 / 50>
3.19
INDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN) & MANUAL LOUVER (BOTTOM)
WIRELESSS OR WIRED MICROCOMPUTER REMOTE CONTROL
477 / 1010
420 / 890
368 / 780
54 / 53 / 52
249 / 9.8
1714 / 67.4
670 / 26.3
345 / 13.6
1816 / 71.4
760 / 29.9
70 / 154
19.1 / 3/4
1605 / 3400
58
852 / 33.6
1030 / 40.6
1010 / 39.8
1180 / 46.5
514 / 20.2
560 / 22.1
95 / 209
FLARE VALVE
9.5 / 3/8
19.1 / 3/4
2.00 / 4.41
37
ALC 40D
39000 / <39000>
11420 / <11420>
3250 / <3220>
17.4 / <5.7>
3.51 / <3.55>
R22
0
1605 / 3400
58
100 / 221
2.40 / 5.29

Hide quick links: