Model - Acson ACM 30D Technical Manual

Ceiling exposed split systems
Table of Contents

Advertisement

(6) ADDITIONAL CHARGE
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below (unit in gram).
R22

Model

10m
28C/CR
94 / 133
030D/DR
133 / 133
035D/DR
130 / 136
040D/DR
134 / 136
050D/DR
130 / 134
061D/DR
245 / 243
R410A
Model
10m
035D/DR
63 / 100
040D/DR
61 / 97
050D/DR
50 / 87
061D/DR
94 / 163
The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual
charge required may be di erent from the guideline due to di erent application and variation in site conditions.
Diagram shows typical charging method.
R22 - Nil
R410A - Nil
12m
15m
173 / 244
291 / 411
243 / 243
409 / 409
238 / 248
400 / 418
245 / 248
412 / 418
238 / 245
400 / 412
450 / 446
756 / 751
12m
15m
116 / 182
195 / 307
112 / 178
189 / 299
92 / 159
155 / 267
173 / 298
290 / 502
26
25m
35m
-
-
962 / 961
1515 / 1514
940 / 983
1481 / 1547
968 / 983
1525 / 1547
942 / 968
1483 / 1525
1778 / 1765
2799 / 2780
25m
35m
457 / 721
720 / 1136
445 / 703
700 / 1107
363 / 628
572 / 989
682 / 1179
1075 / 1857
45m
-
2068 / 2067
2021 / 2112
2081 / 2112
2024 / 2081
-
45m
983 / 1551
956 / 1511
781 / 1350
-