Bus Connector: Enabled And Disabled Terminating Resistor - Siemens SIMATIC S7-300 Hardware And Installation Manual

Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Inserting the bus connector into the module
1. Insert the wired bus connector into the module.
2. Screw-tighten the bus connector on the module.
3. If the bus connector is at the beginning or at the end of a segment, you have to
enable the terminating resistor (Switch position "ON" see figure below).
Note
6ES7 972-0BA30-0XA0 bus connectors are not equipped with a terminating
resistor. You cannot connect it at the beginning or end of a segment.
Please make sure during start-up and normal operation that power is always
supplied to stations where the terminating resistor is active.
Terminating resistance switched on
Figure 6-8 Bus connector: Enabled and disabled terminating resistor
Removing bus connectors
With a looped-through bus cable, you can unplug the bus connector from the
PROFIBUS-DP interface at any time, without interrupting data communication on
the network.
Possible data traffic errors
Warning
Data traffic error might occur on the bus!
A bus segment must always be terminated at both ends with the terminating
resistor. This, for example, is not the case if the last slave with bus connector is off
power. Since the bus connector draws its power from the station, the terminating
resistor has no effect.
Please make sure that power is always supplied to stations on which the
terminating resistor is active.
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
Terminating resistance switched off
on
off
Wiring
on
off
6-17