DP address areas of the CPUs

Table 8-7
DP address areas of the CPUs
Address area
DP address area
for I/Os
Number of those in the I/O
process image
DP diagnostic addresses occupy 1 byte per DP master and DP slave in the input
address area. For example, at these addresses DP standard diagnostics can be
called for the respective node ( LADDR parameter of SFC13). The DP diagnostic
addresses are specified in your configuration. If you do not specify any DP
diagnostic addresses, 7 STEP 7 assigns these DP diagnostic addresses, starting
at the highest byte address downwards .
With CPU 31xC-2DP as master/ CPUx>=3 as master with DPV1 configuration you
assign two different diagnostic addresses to S7 slaves:
• Diagnostic address of the slave (address for slot 0)
At this address all slave events are reported in the DP master (station
representative), e.g. station failure.
• Diagnostic address of the module (address for slot 2)
At this address all module (e.g. CPU 313C-2 DP as I-Slave) events are reported
in the master (OB82). With a CPU as DP-Slave, for example, diagnostic
interrupts for operating mode transitions are reported at this address.
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
315-2 DP
313C-2 DP
314C-2 DP
1024 bytes
2048 bytes
Bytes 0 to 127
Bytes 0 to 127
316-2 DP
318-2 DP
8192 bytes
Byte 0 to 255 (default),
configurable up to
byte 2047
Commissioning
8-25