Section 4
Setting up a project
13.
Click the Next button to open a SAM600 system - Summary Page, see
Summary Page dialog box displays
Number and Available Access Points details. It is possible to cancel the insertion using
Cancel button or confirm the configuration and do the insertion using Finish button.
IEC18000692 V1 EN-US
Figure 20: PCM600: SAM600 system Setup completion wizard
4.6.1

Technical key

Both a SAM600 system and a SAM600 system object in PCM600 have a technical key. The
purpose of the technical key is to prevent from writing a configuration to a wrong SAM600
system. The technical key in SAM600 system and PCM600 must match to write the
configuration. Each SAM600 system in a PCM600 project must have a unique technical key and
therefore it is not possible to set the same technical key for several SAM600 systems in the
same PCM600 project.
22
A SAM600-TS module supports only one redundancy mode at a time: HSR
or PRP.
The default technical key created by PCM600 follows IEC 81346 naming
convention.
The technical key property in PCM600 corresponds to a SAM600 system name
attribute in SCL files. Changing a SAM600 system name attribute value outside
PCM600 may cause the loss of data when SCL files are imported.
© Copyright 2017 ABB. All rights reserved
Custom Name , Module Type , Hardware Type , Serial
1MRK 511 433-UEN B
Figure
20. The
GUID-B9C3EB37-5641-4746-8FCB-B6F088E196FE v1
SAM600 Process Bus I/O System
Engineering manual