Importing Scl Files To Pcm600 - ABB SAM600 Series Engineering Manual

Grid automation process bus i/o system
Hide thumbs Also See for SAM600 Series:
Table of Contents

Advertisement

1MRK 511 433-UEN B
IEC18000668 V1 EN-US
Figure 37: SCL Export Options
5.
Click the Export button to export ICD or CID files to the chosen location.
5.4.2

Importing SCL files to PCM600

PCM600 is able to import SCD, ICD and CID files.
Follow the procedure to import an SCD file to PCM600:
1.
Select the Substation in the Plant Structure.
2.
Right-click on the Substation, and select Import.... The Import window appears.
3.
Select the file to be imported from the saved location.
4.
Click the Open button. The SCL Import Options dialog box appears, see
SAM600 Process Bus I/O System
Engineering manual
All SCL files imported in PCM600 must include the original subnetwork of type
"ABB-USB". In case a System Tool will remove this subnetwork the SCD import
will fail or be refused by PCM600.
© Copyright 2017 ABB. All rights reserved
Section 5
SAM600 Engineering
GUID-2063D54A-8C35-4C54-A4D6-000704207F66 v1
Figure
38.
35