Composition Upgrade Tool - ABB SAM600 Series Engineering Manual

Grid automation process bus i/o system
Hide thumbs Also See for SAM600 Series:
Table of Contents

Advertisement

1MRK 511 433-UEN B
IEC18000661 V1 EN-US
Figure 31:
SMVID, Subnetwork name, Destination MAC address, VLAN ID, VLAN Priority and AppID of
SAM600 streams can be edited from the Object Properties section, see
The minimum length of SMVID is 10 characters and maximum length is 34 characters.
The minimum length of VLAN ID is three characters and characters are limited to 0 to 9
and A to F.
The minimum length of VLAN Priority is one character and characters are limited to 0 to 7.
The minimum length of AppID is four characters and characters are limited to 0 to 9 and A
to F.
5.3

Composition upgrade tool

An existing SAM600 configuration can be modified, extended or updated at any time. This is
achieved using Composition Upgrade Tool which can be launched from a SAM600 system
context menu, see
SAM600 Process Bus I/O System
Engineering manual
PCM600: Modify SAM600 stream fields
For each destination port assignment of any SAM600 stream a new sample
value control block will be instantiated.
For a SAM600 system with single module only three of the available four ports
can be used to send streams. The fourth port will be disabled. Ensure that this
fourth port is not configured in PST as PTP port for time synchronization.
Figure
32.
© Copyright 2017 ABB. All rights reserved
Section 5
SAM600 Engineering
Figure
31.
GUID-711DC837-D063-4B94-93E8-5E495E8D8830 v1
31