Importing Icd Or Cid Files; Object Properties - ABB SAM600 Series Engineering Manual

Grid automation process bus i/o system
Hide thumbs Also See for SAM600 Series:
Table of Contents

Advertisement

Section 5
SAM600 Engineering
IEC18000669 V1 EN-US
Figure 38: SCL Import Options
5.
Configure Import options.
6.
Click the Import button to import SCD file to the PCM600.
5.4.2.1

Importing ICD or CID files

Follow the procedure to import an ICD or CID file to PCM600:
1.
Select the IED in the Plant Structure.
2.
Right-click on the IED, and select Import.... The Import window appears.
3.
Select the file to be imported from the saved location.
4.
Click the Open button. The SCL Import Options window appears, see
5.
Configure Import options. For more information, see
6.
Click the Import button to import ICD or CID files to the PCM600.
5.5

Object properties

When a SAM600 system is selected, its properties are shown in the Object Properties section.
Similarly, when Plant Structure is expanded and objects under it are selected, its properties are
also shown in the Object Properties section, in which some of the field values are editable.
36
Ignore Substation Section to ignore the sub-station section in the SCD file
Select
while importing.
Select
Don't import IEDs of unknown type to disable the import of unknown IED
types (for example third-party IEDs).
Replace unknown IED types with generic IEC 61850 object type to replace
Select
unknown IED types with IED type "Generic IEC 61850 IED". Use this option if you
need to import third-party IEDs into PCM600.
Ignore PCM Object Type if the IED type is modified outside PCM600.
Select
© Copyright 2017 ABB. All rights reserved
1MRK 511 433-UEN B
GUID-3562F273-2415-458C-9BFB-A22D0EF71AA3 v1
Figure
38.
Section
5.4.2.
GUID-0F01F992-7648-4CE9-A733-C46212687B24 v1
SAM600 Process Bus I/O System
Engineering manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sam600-ctSam600-vt

Table of Contents