Hydrogen Sulfide; Exhaust Line; High Pressure Locations; Spm Output Connections - Honeywell SPM Technical Handbook

Single point monitor
Table of Contents

Advertisement

2.3.4 Hydrogen Sulfide (H
Filter
Hydrogen Sulfide Scrubber Filters (P/N 1295K0497)
remove H
S from the sample stream. H
2
interfere when monitoring for gases detected on the
Hydrides, XP Hydrides, or the Hydrogen Cyanide
Chemcassettes. Install the H
sample line as close to the instrument as possible to
permit easy access for visual inspection and replacement
of the filter.

2.3.5 Exhaust Line

The exhaust port (24) uses 3/16" I.D. x 1/4" O.D.
polypropylene tubing.
To install exhaust tubing, push the end of the tube into
the exhaust port (24) until it seats fully inside the fitting
body. To release the tubing, push the small gray collar
in while pulling the tubing out.
Exhaust line length may be up to 10 feet long. Also, make
sure the exhaust line is vented properly.
Sample inlet and exhaust outlet tubing is supplied with
the instrument.

2.3.6 High Pressure Locations

Monitoring in a location with a pressure higher than
that of ambient levels may cause sample gas to be
forced into the instrument and surrounding air during
Chemcassette
advancement. Additional parts are
®
required. Please contact Honeywell Analytics for
application assistance.

2.4 SPM Output Connections

The gas alarm relays, instrument fault relay, and 4-20 mA
output contacts are wired to a 14-pin circular connector
(3). The pin designations are as listed in
SPM Technical Handbook
S) Scrubber
2
S can cross-
2
S Scrubber Filter in the
2
Section 2.4.1.
SPM Single Point Monitor

2.4.1 Output Pin Designations

Pin
Designation
A
Instrument Fault
B
Instrument Fault
C
Instrument Fault
D
Gas Alarm 1
E*
Remote Reset Option
F
Gas Alarm 1
G
Gas Alarm 1
H**
4-20 mA
J
Ground
K**
4-20 mA
L
Gas Alarm 2
M
Gas Alarm 2
N*
Remote Reset Option
P
Gas Alarm 2
B
A
K
K
C
L
J
M
P
D
H
N
E
F
G
* Pins E and N will be open (i.e., no connection) except
on instruments fitted with the Remote Reset option.
See
Section 5.10
** Do not connect analog devices with more than
850 ohm impedance.
Note:
The mA range is 4-20mA and does not indicate when
the unit is in a Fault condition. To receive a fault
indication on the mA output loop the 4-20 mA '+'
signal (H) through the Instrument Fault Common (B)
and use the Instrument Fault Normally Closed (C) as
your 4-20 mA '+' signal. (See above for diagram)
2-4
Conditions
Normally Open
Common
Normally Closed
Normally Closed
Common
Normally Open
(+)
(-)
Normally Closed
Common
Normally Open
4-20mA -
Signal to/from HA controllers or PLC
B
A
4-20mA +
C
L
J
P
M
D
H
N
E
F
G
Jumper wire from pin "H" to pin "C"
for more information.