Metso neles ND9000H Installation, Maintenance And Operation Instructions page 6

Intelligent valve controller
Hide thumbs Also See for neles ND9000H:
Table of Contents

Advertisement

6
Ui ≤ 32 V
Ex nL IIC:
Ii ≤ 380 mA
Pi ≤ 5.32 W
Ci ≤ 5 nF
Li ≤ 10 µH
(Ex approvals are valid under these conditions)
FOUNDATION Fieldbus function block execution times
ND9000F
AO
20 ms
PID
25 ms
DO
15 ms
DI
15 ms
IS
15 ms
OS
20 ms
Performance with moderate constant-load actuators
EC05-EC10 in ambient temperature
Values at 20 °C / 68 °F and without any additional instru-
ments, such as boosters or quick exhaust valves etc.
Dead band acc. to IEC 61514:
≤ 0.1 %
Hysteresis acc. to IEC 61514:
< 0.5 %
Local user interface functions
Local control of the valve
Monitoring of valve position, input signal, temper-
ature, supply and actuator pressure difference
Guided start-up function
LUI may be locked remotely to prevent unauthor-
ised access
Calibration: Automatic/Manual/Linearization
1-point calibration
Control configuration: aggressive, fast, optimum,
stable, maximum stability
Mode selection: Automatic/Manual
Rotation: valve rotation clockwise or counter-
clockwise to close
Dead angle
Low cut-off, cut-off safety range (default 2 %)
Positioner fail action, open/close
Signal direction: Direct/reverse acting
Actuator type, double/single acting
Valve type, rotary/linear IEC/nelesCV Globe/FLI
Language selection: English, German and French
Approvals
ND9100H, ND9100F and ND9100P
ND9300H, ND9300F and ND9300P
Intrinsically safe and non incendive
IECEx
IEC 60079-0: 2007-10 , IEC 60079-11: 2006,
IEC 60079-26: 2006, IEC 60079-27: 2005-04,
IEC 61241-0: 2004, IEC 61241-1: 2004
Ex ia IIC T4/T5/T6 Ga
Ex tD A20 IP66 T90°C
or
Ex ia IIC T4/T5/T6 Gb
Ex tD A21 IP66 T90°C
IEC 60079-0 :2007-10, IEC 60079-15: 2005-03,
IEC 60079-27: 2005-04, IEC 61241-0 :2004,
IEC 61241-1: 2004
Ex nA IIC T4/T5/T6 Gc
Ex tD A22 IP66 T90°C
or
Ex nL IIC T4/T5/T6 Gc
Ex tD A22 IP66 T90°C
Certificates IECEx VTT 10.0004X
and IECEx VTT 10.0005X
ATEX
EN 60079-0: 2007/2009, EN 60079-11: 2007,
EN 60079-26: 2007, EN 60079-27: 2006,
EN 61241-0: 2006, EN 61241-1: 2004
II 1G Ex ia IIC T4/T5/T6 Ga
II 1D Ex tD A20 IP66 T90°C
or
II 2 G Ex ia IIC T4/T5/T6 Gb
II 2 D Ex tD A21 IP66 T90°C
EN 60079-0: 2007/2009, EN 60079-15: 2005,
EN 60079-27: 2006, EN 61241-0: 2006
EN 61241-1: 2004
II 3 G Ex nA IIC T4/T5/T6 Gc
II 3 D Ex tD A22 IP66 T90°C
or
II 3 G Ex nL IIC T4/T5/T6 Gc
II 3 D Ex tD A22 IP66 T90°C
Certificates VTT 09 ATEX 033X and
VTT 09 ATEX 034X
CSA
CAN/CSA-C22.2-0,-142, -157;
CAN/CSA-E60079-0,-11, -15
IS Class I, Div. 1, Groups A, B, C, D T4...T6
IS Class I, Zone 0, Ex ia IIC T4...T6
NI Class I, Div. 2, Groups A, B, C, D T4...T6
FM
FM Class 3600, 3610, 3611, 3810,
ANSI/ISA-60079-0, 60079-11:
IS Class I, Div. 1, Groups A, B, C, D T4...T6
IS Class I, Zone 0, AEx ia IIC T4...T6
NI Class I, Div. 2, Groups A, B, C, D T4...T6
NI Class I, Zone 2, Ex nA IIC T4...T6
INMETRO
IEC 60079-0, IEC 60079-11, IEC 60529
BR-Ex ia IIC T4/T5/T6 IP66
or
IEC 60079-0, IEC 60079-15, IEC 60529
BR-Ex nA II / nL IIC T4/T5/T6 IP66
ND9200H, ND9200F and ND9200P
ND9300H, ND9300F and ND9300P
Flameproof, explosion proof and dust exclusion
ATEX
EN 60079-0: 2006, EN 60079-1: 2004
EN 61241-0: 2006, EN 61241-1: 2004
II 2 G Ex d IIC T4...T6
II 2 D Ex tD A21 IP66 T100°C
Certificate KEMA 04ATEX2098 X