Discharge Pipe Work - andrews BUFFER-GL200-8 Installation And Service Manual

Glass lined buffers
Table of Contents

Advertisement

Discharge Pipe work

It is a requirement of Building Regulations that any discharge from an unvented system is
conveyed to where it is visible, but will not cause danger to persons in or about the building.
The tundish and discharge pipes should be fitted in accordance with the requirements and
guidance notes of Building Regulations. Building Regulation G3 Requirements and Guidance
section 2 (page 17) are reproduced in the previous sections.
For discharge pipe arrangements not covered by G3 Guidance advice should be sought from
your local Building Control Officer. Any discharge pipe connected to the pressure relief
devices (Expansion Valve and Temperature / Pressure Relief Valve) must be installed in a
continuously downward direction and in a frost free environment.
The water may drip from the discharge pipe of the pressure relief device and that this pipe
must be left open to the atmosphere. The pressure relief device is to be operated regularly to
remove lime deposits and to verify that it is not blocked.
G3 Requirement
"...there shall be precautions...to ensure that the hot water discharged from safety devices is
safely conveyed to where it is visible but will not cause danger to persons in or about the
building".
Worked example of discharge pipe sizing (Taken from Building Regulations 2000, G3,
2010 edition)
The example below is for a G1" temperature relief valve with a discharge pipe (D2) having 4 No.
elbows and length of 7m from the tundish to the point of discharge.
From Table 5:
Maximum resistance allowed for a straight length of 35mm copper discharge pipe (D2) from a
G1" temperature relief valve is 9m.
Subtract the resistance for 4 No. 35mm elbows at 1.4m each =
5.6m Therefore the permitted length equates to: 3.4m
3.4m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 42mm pipe (D2) from a G1" temperature
relief valve equates to 18m.
Subtract the resistance of 4 No. 42mm elbows at 1.7m each =
6.8m Therefore the maximum permitted length equates to: 11.2m
As the actual length is 7m, a 42mm (D2) copper pipe will be satisfactory.
16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents