Message Receivers - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Services

Message receivers 1...4

28 / 176
Siemens
Building Technologies
Path: Home > 0.5 OZW672... > Settings > Communication > Services
Data point
ACS access
Default value: On
Setting values: On/Off
Web access via http
Default value: Off
Setting values: On/Off
UPnP localization
Default value: Ethernet
Setting value: ---, Ethernet,
USB
ETS access via
KNXnet/IP
Default value:On
Setting values:On/Off
Portal connection
Default value: On
Setting values: On/Off
Automatic
log off
Default value: On
Setting values: On/Off
2.5.3.4
Message receivers
Data points are available for function checks of message receivers. They are
available under the following path:
Path: Home > 0.5 OZW772... > Settings > Message receivers
The use of these data points (test message receivers, send system report, reason,
message suppression) is described in Section 2.7, Functional check.
Message receivers must be defined if the Web Server sends fault messages via
email.
Settings can be made separately for 4 message receiver:
Path: Home > 0.2.150 OZW772.xx > Settings > Message receiver >
Web server OZW772... V6.0
Commissioning
Explanation, example
Permits access by ACS operating software to
the Web Server (only possible via direct
connection – not possible via the portal). For
security reasons, ACS access should be
switched off after commissioning.
Permits communication using the http protocol
rather than the secured https connection.
Siemens recommends https. The user is
responsible for using http.
The Web-Server registers its existence in the
corresponding network using the Universal
Plug and Play (UPnP) service.
Permits access to the plant using ETS software
via KNXnet/IP (using direct connection only –
not possible via portal)
"On" enables data exchange with the portal. No
data is exchanged under "Off".
The connection to Web Server automatically
times out after 24 hours.
CE1C5701en
2015-10-12