Communication - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

KNX
Siemens
Building Technologies
2.5.3.3

Communication

Path: Home > 0.2.150 OZW772.xx > Settings > Communication > KNX
Data point
Range
Line
Device address
Default val: 150
Setting val: 1... 253
Time synchronization
Default value: Slave on bus
Setting values: Slave on Bus
Quartz
Clock time mode KNX
Default val: Autonomous
Setting val: Autonomous/Master
Clock slave remote adj
KNX
Default val: Yes
Setting val: Yes / No
The following data points are information parameters. They are described in
Section 4.2.3, "Web Server diagnostics":
· Maximum number of devices
· Current number of devices
· Last change
Web server OZW772... V6.0
Commissioning
Explanation, example
Displays the range within the KNX bus.
e.g. 0 for address 0.2.150
The range is set in ETS.
Display of line within the KNX bus.
e.g. 2 for address 0.2.150
The line is set in ETS.
Set device address. The device address must
be unique within the same KNX line.
Defines time synchronization on the Web
Server. Default value "Slave on bus": Clock
master is available on the KNX network.
Setting value "Quartz": The clock is
synchronized with quartz on the Web Server.
Web Server operates a clock master or
autonomously.
"Slave" for "Time synchronization" = "Slave on
bus".
For "Time synchronization" = "Quartz", can
selected between "Autonomous" or "Master".
Setting value is important for "Time
synchronization" = "Slave on bus".
For "Clock slave remote adj KNX" = "Yes" the
time clock for the clock master on the KNX
network can be changed via the time clock for
the Web Server.
— —
— —
25 / 176
CE1C5701en
2015-10-12