Table 79. DS8880 power cords (continued)
Power cord feature
Power cord description
code
1088
Three-phase WYE (3ØY)
4
voltage (five-wire 3+N+PE),
380-415V~ (nominal line-to-line
(LL)), 40 A, no customer
connector provided
(pre-stripped wires, termination
ready for EMEA (except Japan),
hard-wired, or uses client
provided customer
connector/plug as regionally
allowed)
1089
Three-phase Delta (3Ø∆)
1, 4, 5
voltage (four-wire 3+PE
(Protective Earth Ground)),
200-240V, 60 A, IEC 60309 4-pin
customer connector with
IEC'309 service ready plug, for
United States, Canada, Latin
America, Japan, and Taiwan
(EMEA and other regions can
optionally order)
Notes:
1. The customer connector must be IEC 60309-compliant. Power cords that are used with DS8100, DS8300, DS8700,
DS8800, and DS8870 cannot be used again with the DS8880.
2. Power cords without inline connectors are rated at 600 V AC. Other power cords are rated as described in the
table. Single-phase power cord has 2W+G configuration.
3. The conductor size for single-phase power cords is 10 mm
4. Power cords that exit the bottom are 4.2 m (14 ft) from the lowest point where they exit the frame to the mating
face of the plug or bare leads. Power cords that exit the top are 1.8 m (6 ft) from the highest point from the
frame to the mating face of the plug or bare leads.
5. The IEC60309 receptacle must be installed in a metal-backed box with the green wire ground-connected to the
grounding lug within the box. Ensure continuity between the box and the metallic shielding of the liquid-tight
conduit.
6. The descriptions indicate the line cord rating and are not an indication of system power rating. The cord rating
defines the maximum breaker rating for the line cord (60A with connector, 63A without connector). Downstream
components are designed for fault currents consistent with facility circuit breaker ratings up to 63A.
The following shows the plug (connector on the line cord).
Figure 26. Single-phase, 200 - 240 V, 60A, IEC60309 cable connector pins
160
DS8880 Introduction and Planning Guide
6
B
A
Vac
Vac
G
Inline connector
Receptacle
Not applicable
Not applicable
HBL460C9W, Pin and
HBL460R9W, AC
Sleeve Connector, IEC
Receptacle, IEC
309, 3P4W
60309, 3P4W
2
(8 awg).
Wire gauge
6 mm² (10
AWG)
10 mm² (8
AWG)