Huawei TP48200A-HT15D3 User Manual page 79

Outdoor power system
Hide thumbs Also See for TP48200A-HT15D3:
Table of Contents

Advertisement

TP48200A-HT15D3 Outdoor Power System (Russia,
Megafon)
User Manual
Item
DC output
AC input protection
DC output
protection
AC surge protection
DC surge protection
Safety and
regulatory design
Mean time between
failures (MTBF)
Issue 02 (2019-02-26)
Specifications
(THD)
Output voltage range
Default output voltage
Output power
Regulated voltage precision
Ripple and noise
Psophometrically weighted
noise
Current sharing imbalance
AC input overvoltage
protection threshold
AC input overvoltage
recovery threshold
AC input undervoltage
protection threshold
AC input undervoltage
recovery threshold
DC output overvoltage
protection threshold
Nominal lightning strike discharge current: 20 kA (8/20 µ s);
maximum lightning strike discharge current: 40 kA (8/20 µs)
Differential mode: 10 kA (8/20 μs); common mode: 20 kA (8/20
μs)
IEC/EN60950-1
200,000 hours (at 30℃)
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
–42 V DC to –58 V DC
–53.5 V DC
Maximum output power = Output
power of a single rectifier x
Number of rectifiers
≤ ±1%
≤ 200 mVp-p
≤ 2 mV
< ± 5% (20%–100% load)
> 300 V AC
When the voltage is restored to 290
V AC, the output resumes.
< 85 V AC
When the voltage is restored to 90
V AC, the output resumes.
–58.5 V DC to –60.5 V DC
If overvoltage occurs due to an
internal fault, the rectifier locks
out.
If the external voltage is higher
than –63 V DC for more than
500 ms, the rectifier locks out.
72