Eev Kit Installation; Introduction, Specifications, And Design Parameters - LG PAHCMR000 Installation Manual

Hide thumbs Also See for PAHCMR000:
Table of Contents

Advertisement

Introduction
When used with the LG AHU Communications Kit (sold separately), the LG EEV Kit controls refrigerant flow between
LG Multi V air-source or water-source units and a third-party air handler unit (AHU).
The EEV Kits for PAHCMR000 are offered in three sizes:
• PRLK048A0 supports 12 through 96 MBH (8 tons maximum)
• PRLK096A0 supports 96.1 through 192 MBH (16 tons maximum)
• PRLK396A0 supports 192.1 MBH through 396 MBH (32 ton maximum)
Specifications
Table 9: EEV Kit Specifications Table.
Model Number
For Use With
Power Supply Requirements Powered by Air Handler Unit Comm Kit (12 VDC)
Ambient Opera�ng
Temperature Range
Ambient Opera�ng
Humidity Range
Dimensions (in., W x H x D)
Net Weight (lbs.)
Shipping Weight (lbs.)
Maximum Air Handler Unit
Capacity (Btu/h)
Communica�ons Cable
Refrigerant Type
Table 10: EEV Kit Compatibility Table.
EEV Kit
PRLK048A0
(8 tons max)
PRLK096A0
(16 tons max)
PRLK396A0
(32 tons max)
PRLK594A0
(48 tons max)
EEV Kit Design Parameters
• Maximum of one (1) EEV Kit can be connected to one (1) AHU
Communications Kit.
• Minimum coil entering air temperature for heating mode is 41°F.
• Requires field-supplied six-conductor communication cable to
connect to AHU Communications Kit.

Introduction, Specifications, and Design Parameters

PRLK048A0
PRLK096A0
PAHCMR000 and PAHCMS000
0 to 98% (Non-condensing)
8-5/8 x 15-15/16 x 3-5/16
6.8
7.9
96,000
AWG 18 x 6 Stranded, Shielded Copper Wire
AHU Communica�on Kit
PAHCMR000
PAHCMS000
HP/HR
HP
HP
HP
HP
HP
HP (requires EEV
NA
module)
HP = Heat Pump; HR = Heat Recovery
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

EEV KIT INSTALLATION

PRLK396A0
- 4 to 149F
13-25/32 x 7-3/32
x 13-39/64
-
11.0
12.1
192,000
396,000
R410A
• Maximum distance between EEV Kit and AHU Communications Kit
is thirty-two (32) feet.
• Designed for indoor installations (field-supplied waterproof enclo-
sure must be used when installing outdoors).
Figure 16: EEV Kit.
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents