Eev Kit Installation; Introduction, Specifications, And Design Parameters - LG PAHCMS000 Installation Manual

Air handler unit communications kit
Hide thumbs

Advertisement

Introduction
When used with the LG AHU Communications Kit (sold separately), the LG EEV Kit controls refrigerant flow between
LG Multi V air-source or water-source units and a third-party air handler unit (AHU).
The EEV Kits for PAHCMS000 are offered in four sizes:
• PRLK048A0 supports 12 through 96 MBH (8 tons maximum)
• PRLK096A0 supports 96.1 through 192 MBH (16 tons maximum)
• PRLK396A0 supports 192.1 MBH through 396 MBH (32 ton maximum)
• PRLK594A0 supports 396.1 MBH through 594 MBH coils (48 ton maximum, requires EEV Controller
Module PAEEVA020).
Specifications
Table 13: EEV Kit Specifications Table.
Model Number
For Use With
Power Supply Requirements
Ambient Opera�ng
Temperature Range
Ambient Opera�ng
Humidity Range
Dimensions (in., W x H x D)
Net Weight (lbs.)
Shipping Weight (lbs.)
Maximum Air Handler Unit
Capacity (Btu/h)
Communica�ons Cable
Refrigerant Type
Table 14: EEV Kit Compatibility Table.
EEV Kit
PRLK048A0
(8 tons max)
PRLK096A0
(16 tons max)
PRLK396A0
(32 tons max)
PRLK594A0
(48 tons max)
EEV Kit Design Parameters
• Maximum of one (1) EEV Kit can be connected to one (1) AHU
Communications Kit.
• Minimum coil entering air temperature for heating mode is 41°F.
• Requires field-supplied six-conductor communication cable to
connect to AHU Communications Kit.

Introduction, Specifications, and Design Parameters

PRLK048A0
PRLK096A0
PAHCMR000 and PAHCMS000
Powered by Air Handler Unit Communica�ons Kit (12 VDC)
8-5/8 x 15-15/16 x 3-5/16
6.8
7.9
96,000
AWG 18 x 6 Stranded, Shielded Copper Wire
AHU Communica�on Kit
PAHCMR000
PAHCMS000
HP/HR
HP
HP
HP
HP
HP
HP (requires EEV
NA
module)
HP = Heat Pump; HR = Heat Recovery
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

EEV KIT INSTALLATION

PRLK396A0
-4 to 149F
0 to 98% (Non-condensing)
13-25/32 x 7-
3/32 x 13-39/64
11.0
12.1
192,000
396,000
R410A
• Maximum distance between EEV Kit and AHU Communications Kit
is thirty-two (32) feet.
• Designed for indoor installations (field-supplied waterproof enclo-
sure must be used when installing outdoors).
Figure 16: EEV Kit.
PRLK594A0
PAHCMS000 with
EEV Controller
Module
PAEEVA020
16-1/8 x 7-3/32 x
13-39/64
15.4
16.5
594,000
45