AIREDALE LogiCool LCC20 Technical Manual page 6

Freecooling chiller 20kw - 40kw
Table of Contents

Advertisement

LOGICOOL™
General Description
STANDARD FEATURES - ENERGY SAVING
Evaporator
Condenser
Free-Cooling Coil
Fan & Motor Assembly
Head Pressure Control
Chillers
6
Technical Manual : 6521355 V1.14.0 11/2016
Stainless steel high efficiency brazed plate heat exchanger(s) will allow optimum heat
transfer between media. Each heat exchanger is insulated with closed cell polyurethane
foam to Class 1 fire rating and the material is UV resistant.
A self-regulating pad heater is fitted to the single evaporator and will protect against
freeze up in ambient temperatures as low as -20°C.
Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,
manufactured from refrigeration quality copper tubes with mechanically bonded
aluminium fins.
The copper tube is internally rifled for improved heat transfer.
Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,
manufactured from refrigeration quality copper tubes with mechanically bonded
aluminium fins.
Spacing between condenser and free-cooling coils is provided for cleaning maintenance
along with top access holes and drain holes to the base.
Sickle bladed fan assemblies with integral long bellmouth and fingerproof grille;
incorporate external rotor ac motor technology, capable of highly accurate discreet speed
control, discharges air vertically. The fans offer maximum airflow performance while
keeping sound levels to a minimum.
Each fan is speed controllable and operates from a 3 phase electrical supply.
Energy efficient Electronically Commutated (EC) fans are also available; refer to
on page 8.
Extras - Energy Saving,
3 phase head pressure controllers are fitted which modulate the fan speed to maintain a
constant condensing pressure in the DX mechanical cooling mode and afford reductions
in input power when overcooling in low ambients.
A pressure transducer is fitted to the liquid line which in turn feeds back the head
pressure to the microprocessor. The condenser fan speed can then modulate via the
controller to provide optimum control under varying ambient conditions. The head
pressure can be monitored via the display keypad.
Additional refrigeration valves are fitted to allow mechanical and free-cooling functions to
operate simultaneously in order to maximise free-cooling and minimise
energy consumption.