SITRANS F M electromagnetic flowmeter type MAG 1100 F, DN 10 - DN 100 3/8" - 4"
Installation, thread type
adapter
Self-draining
Installation of the cover or
transmitter on the termi-
nal box
Installation, cable
8
Sensor, gaskets and adapters are assem-
bled to one unit and then installed in the
pipeline prepared with a suitable fitting.
Standard gaskets for the actual thread con-
nection must be used.
Tightening must be performed with a suitable
union spanner.
For applications where self-draining is re-
quired, the sensor must be mounted with a
minimum incline of 15° to the horizontal
plane.
1. Mount the cover or the transmitter on the
terminal box.
2. It is important that the screws are firmly
tightened (4 Nm). Use a large screwdriver
fitting into the screw slot.
Tighten the cable glands and the cable en-
tries to obtain optimum sealing. The cable
entry gasket must obtain firm contact with the
cable.