CAUTION SIGNS

Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water
drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water
leakage.
When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m away from the electric
appliances and install it at least 2m away from the lightning conductor.
Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
Make sure that the pipes does not get any weaker by welding it too much.
Make sure to install the product away from children's' reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease product's performance.)
Lighting rod
Protective angle:
25˚~55˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
If you use the wireless remote control, it may not operate normally due to ballast stabilizer.

Do not install the product in following places.

Place where outdoor unit's noise and warm air may disturb neighbors. (It may cause property loss.)
Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The efficiency of the heat exchanger may reduce or product may break.
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of fire or explosion.)
The place with carbon fiber or flammable dust.
The place near seashore or hot spring where there is risk of outdoor unit corrosion.
Height of the building
20m or less
40m or less
60m or less
Protection control
55˚
35˚
25˚
5