Connecting The Flared Pipes - Samsung DVM S Series Installation Manual

Table of Contents

Advertisement

Refrigerant pipe installation

Connecting the flared pipes

Check if the flaring is properly done according to the standard size.
Align the center of the piping and tighten the flare nut with your hands. Then, tighten the flare nut with torque wrench in
a direction of the arrow indicated in below illustration.
Make sure to use ester oil to coat the flare connection section.
Flare connection section
Outer diameter (D, mm)
Ø 6.35
Ø 9.52
Ø 12.70
Ø 15.88
Ø 19.05
• Blowing Nitrogen gas should be done when welding the pipe.
• Make sure to use the provided flare nut.
CAUTION
• Make sure that there are no cracks or twisted part when you need to bend the pipe.
• Do not fasten the flare nut with excessive strength.
• R-410A is a high pressure refrigerant and there is a risk of refrigerant leakage if the flare connection is not coated
with ester oil. Therefore, apply ester oil to coat the flare connection area.
46
Pipe
Flare nut
Connection torque (N·m)
14~18
34~42
49~61
68~82
100~120
Monkey wrench
Torque wrench
Flare dimension (L, mm)
8.7~9.1
12.8~13.2
16.2~16.6
19.3~19.7
23.6~24.0
Flare shape (mm)
R 0.4~0.8
D
L

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm s am080fxvaghDvm s am fxvagr seriesDvm s am100fxvaghDvm s am120fxvaghDvm s am160fxvaghDvm s am140fxvagh ... Show all

Table of Contents