Step 6 Connecting The Assembly Pipes To The Refrigerant Pipes - Samsung AC TNCDKC Series Installation Manual

Table of Contents

Advertisement

D
A
Pipe
Flare
Outer Diameter (D)
Depth (A)
Ø6.35 mm
1.3 mm
Ø9.52 mm
1.8 mm
Ø12.70 mm
2.0 mm
Ø15.88 mm
2.2 mm
Ø19.05 mm
2.2 mm
5 Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Damaged
Correct
Inclined
Surface
Step 6 Connecting the assembly
pipes to the refrigerant pipes
There are two refrigerant pipes of different diameters :
A smaller one for the liquid refrigerant.
A larger one for the gas refrigerant. The inside of copper
pipe must be clean and has no dust.
1 Remove the pinch pipe on the pipes and connect the
assembly pipes to each pipe, tightening the nuts, first
manually and then with a torque wrench, a spanner
applying the following torque.
R 0.4 to 0.8 mm
D
L
Flare
Flare dimension (L)
8.7 to 9.1 mm
12.8 to 13.2 mm
16.2 to 16.6 mm
19.3 to 19.7 mm
23.6 to 24.0 mm
Uneven
Cracked
Thickness
1
Spanner
3
Union
Outer diameter (mm)
Ø6.35
Ø9.52
Ø12.70
Ø15.88
Ø19.05
NOTE
If the pipes must be shortened, see Step 5 Cutting and
flaring the pipes on page 8.
2 Be sure to use an insulator thick enough to cover the
refrigerant tube to protect the condensate water on the
outside of the pipe falling onto the floor and to improve
the efficiency of the unit.
3 Cut off any excess foam insulation.
4 Make sure that there are no cracks or waves on the bent
area.
5 It would be necessary to double the insulation thickness
(10 mm or more) to prevent condensation even on the
insulator when if the installed area is warm and humid.
2
Torque
3
wrench
Flare nut
Torque (N•m)
14 to18
34 to 42
49 to 61
68 to 82
100 to 120
(1 N•m=10 kgf•cm)
9
English