D9024/D10024

Networking Guide

Notice

The material and instructions covered in this manual have been carefully checked for accuracy and are
presumed to be reliable. However, the manufacturer assumes no responsibility for inaccuracies and
reserves the right to modify and revise this document without notice.
These instructions are for connecting, programming, and operating D9024 and D10024 Fire Alarm
Control Panels in a network controlled by a D9024 or D10024 master panel. See the D9024 and D10024
Installation, Operation, and Programming Instructions for specific information on individual D9024 and
D10024 Fire Alarm Control Panel Systems.

Warnings and Cautions

Warning: is used in these instructions to indicate procedures to follow to avoid injury.
Caution:
is used in these instructions to indicate procedures to follow to avoid damage to
equipment.

FCC Notices

Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a commercial installation. This equipment generates, uses and can radiate radio
frequency energy, and, if not installed in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment on and off, the user is encouraged to try to correct the
interference by one or more of the following measures:
1) Reorient or relocate the receiving antenna
2) Increase the separation between the equipment and the receiver
3) Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
4) Consult the dealer or an experienced radio/TV technician for help.

UL/NFPA Notices

UL listed for NFPA 72, Local.
All references to NFPA and related requirements are based upon compliance with the 1993 edition of
NFPA 72, National Fire Alarm Code. Since installation specifications are nearly always based upon a
specific edition of a standard that has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier
editions of NFPA standards will generally apply. Consult with the appropriate AHJ for confirmation.
©1997 Radionics
™The Radionics logo is a registered trademark of Radionics,
1800 Abbott Street, Salinas, CA 93901, USA
Analog Fire Alarm Control Panel
All rights reserved
34377B
04/97
D9024/D10024
Networking Guide
Page 1 of 18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D9024 and is the answer not in the manual?

Questions and answers

Summary of Contents for Radionics D9024

  • Page 1: Networking Guide

    These instructions are for connecting, programming, and operating D9024 and D10024 Fire Alarm Control Panels in a network controlled by a D9024 or D10024 master panel. See the D9024 and D10024 Installation, Operation, and Programming Instructions for specific information on individual D9024 and D10024 Fire Alarm Control Panel Systems.
  • Page 2: Table Of Contents

    Figure 28: Commission Menu Three......................10 Figure 29: Master Panel Fault Condition Display ..................11 ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 2 of 18...
  • Page 3 Table of Tables Table 1: Shared Zone Configuration ......................5 ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 3 of 18...
  • Page 4: Network Installation

    A. Network Installation All panels must be D9024 or D10024 Fire Alarm Control Panels. The network wiring is supervised. A fault in the network wiring results in a warning message. In a fault condition on the network wiring each panel will operate as a stand-alone unit.
  • Page 5: Shared Zone Network Operation

    The operator may use the control keys on any panel to respond to alarm and fault conditions. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 5 of 18...
  • Page 6: Shared Zone Network Programming

    To do this, run the setup sequence, Section C.1. of the D9024/D10024 Programmer’s Guide, on each panel and set the Memory Lock Check, Section C.1.h. , to [No]. Leave the memory lock switch in the unlocked position.
  • Page 7: Figure 6: Network Menu One

    Figure 10: Network Menu Five Press YES. The panel displays Network Menu Six. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 7 of 18...
  • Page 8: B.2.B. Slave Panel Programming, Shared Zone Network

    4) Enable 5)Disable 6)Print 7)View Figure 16: Commission Menu One ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 8 of 18...
  • Page 9: Figure 17: Commission Menu Three

    Figure 21: Network Menu Five Press YES. The panel displays Network Menu Six. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 9 of 18...
  • Page 10: Figure 22: Network Menu Six

    Press 3)NORMAL OPERATION to return to the Operator’s Menu, Mail Level. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 10 of 18...
  • Page 11: Report And Control Network

    The Report and Control Network links the individual panels to a master panel for reporting and control. Up to 10 D9024 and/or D10024 panels may be networked together in a Report and Control Network with one dedicated panel designated to act as the Master.
  • Page 12: Report And Control Network Programming

    To do this, run the setup sequence, Section C.1. of the D9024/D10024 Programmer’s Guide, on each panel and set the Memory Lock Check, Section C.1.h. , to [No]. Leave the memory lock switch in the unlocked position.
  • Page 13: Figure 32: Main Menu

    Enter the number of slave processors (1 to 9 in a report and control network). The panel displays Network Menu Three ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 13 of 18...
  • Page 14: Figure 36 Network Menu Three

    Port B Protocol should be set to zero. Press YES. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 14 of 18...
  • Page 15: C.2.B. Slave Panel Programming, Report & Control Network

    1)Day Modes 2)Setup options 3)Network [1] Figure 46: Commission Menu Three ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 15 of 18...
  • Page 16: Figure 47: Network Menu One

    Set Remote Alarms to [FALSE] on all sub panels. Enter YES. The panel displays Network Menu Seven. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 16 of 18...
  • Page 17: Figure 53: Network Menu Seven

    Memory Lock Check (Section C.1.h.) to [Yes] on the Master Panel and each Slave Panel. ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 17 of 18...
  • Page 18: Panel Programming Options

    PC Interface Two-way interface with acknowledgment PC Interface One-way interface ©1997 Radionics 34377B 04/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Networking Guide 1800 Abbott Street, Salinas, CA 93901, USA Page 18 of 18...