Radionics D9024 Installation Instructions Manual

Analog control panels
Hide thumbs Also See for D9024:
Table of Contents

Advertisement

Quick Links

D9024 and D10024
Installation Instructions

Notice

The material and instructions covered in this manual have been carefully checked for accuracy and are
presumed to be reliable. However, the manufacturer assumes no responsibility for inaccuracies and
reserves the right to modify and revise this document without notice.
These instructions cover the installation of the D9109A Enclosure and the installation of the D9024 or
D10024 system components within it. See the Fire Alarm Control Panel Operator's Manual for
instructions on powering up and operating the system.

Warnings and Cautions

Warning
is used in these instructions to indicate procedures to follow to avoid injury.
Caution
is used in these instructions to indicate procedures to follow to avoid damage to
equipment.

FCC Notices

Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a commercial installation. This equipment generates, uses and can radiate radio
frequency energy, and, if not installed in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment on and off, the user is encouraged to try to correct the
interference by one or more of the following measures:
1) Reorient or relocate the receiving antenna
2) Increase the separation between the equipment and the receiver
3) Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
4) Consult the dealer or an experienced radio/TV technician for help.
UL/NFPA Notices
UL listed for NFPA 72, Local
All references to NFPA and related requirements are based upon compliance with the 1993 edition of
NFPA 72, National Fire Alarm Code. Since installation specifications are nearly always based upon a specific
edition of a standard which has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier
editions of NFPA standards will generally apply. Consult with the appropriate AHJ for confirmation.
www.PDF-Zoo.com
Analog Fire Alarm Control Panels
©1997 Radionics
™The Radionics logo is a registered trademark of Radionics,
1800 Abbott Street, Salinas, CA 93901, USA
firealarmresources.com
All rights reserved
74-07649-000-B
01/97
D9024/D10024 Installation
Page 1 of 17

Advertisement

Table of Contents
loading

Summary of Contents for Radionics D9024

  • Page 1: Notice

    These instructions cover the installation of the D9109A Enclosure and the installation of the D9024 or D10024 system components within it. See the Fire Alarm Control Panel Operator’s Manual for instructions on powering up and operating the system.
  • Page 2: Table Of Contents

    C.3.a. D9051 Module Installation ......................11 C.3.b. D10024 Attachment Points ......................11 C.3.c. D9024 Attachment Ports .......................11 C.3.d. D9051 Module Connection to the Control Module .................12 C.3.e.
  • Page 3 Figure 1: D9109A Enclosure and Removable Door ..................4 Figure 2: Ground Location on Control Module .....................5 Figure 3: Output Connection Points on the D9024 and D10024M Control Module ........6 Figure 4: D10024M Control Module ......................7 Figure 5: Enclosure Connections ........
  • Page 4: D9109A Enclosure Installation

    System Wiring Figure 1: D9109A Enclosure and Removable Door ©1997 Radionics 74-07649-000-B 01/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Installation Page 4 of 17 1800 Abbott Street, Salinas, CA 93901, USA www.PDF-Zoo.com firealarmresources.com...
  • Page 5: Circuit Connections

    B. Circuit Connections The D9024 and D10024 Fire Alarm Control Panels (FACP) are analog systems. They exchange data and may provide power to devices over two-wire circuits. Radionics recommends shielded single pair twisted cable wiring with a drain wire such as Atlas #218 or West Penn Wire/CDT #D293.
  • Page 6: Peripheral Circuits

    Part No. 73-07674-000-A, for devices acceptable for use in the indicating circuit. The D9024 and D10024 each has terminals for a power-limited auxiliary 24 V circuit at the lower left of the Control Module. This circuit is rated at one Amp maximum. If the system requires more than four circuits use the D327 Indicating Circuit Module to add circuits as required.
  • Page 7: Control Panel Components

    Control Module. Connect the Display Panel Ground Strap to the enclosure ground stud. See Figure 5. ©1997 Radionics 74-07649-000-B 01/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Installation Page 7 of 17 1800 Abbott Street, Salinas, CA 93901, USA www.PDF-Zoo.com firealarmresources.com...
  • Page 8: D9067 Polling Circuit Module

    C.2. D9067 Polling Circuit Module Analog measuring devices report to the FACP over a polling circuit that connects to a D9067 Polling Circuit Module. The D10024 has five expansion slots for the D9067. The D9024 has three. (See Figure 6.) C.2.a.
  • Page 9: C.2.B. D9067 Module Connection To The Control Module

    Module Figure 8: D9067 Class “B” (Style 4) Connection ©1997 Radionics 74-07649-000-B 01/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Installation Page 9 of 17 1800 Abbott Street, Salinas, CA 93901, USA www.PDF-Zoo.com firealarmresources.com...
  • Page 10: C.2.D. D9067 Module Connection To Class "A" (Style 6) Circuit

    Class A, Style 6 data interface between the Control Module and Command Centers, Annunciators, networked panels, serial peripherals, and computer graphics systems. The D9024 and D10024 Fire Alarm Control Panels can support up to 31 peripheral communications devices on the RS485 bus. Each device must be assigned an individual binary address.
  • Page 11: C.3.A. D9051 Module Installation

    C.3.c. D9024 Attachment Ports On the D9024 Ports B, C, and D are the three ports on the left side of the board. Port B is below the 10-wire ribbon socket labeled PL_LOOP3 and Ports C and D are reserved for peripheral devices only.
  • Page 12: C.3.D. D9051 Module Connection To The Control Module

    120V input connection. Radionics recommends that only a licensed electrician make 120 V AC connections to the D10024 System. All connections are to conform to NFPA 70/NEC. Connect the D10024 system to a suitable ground.
  • Page 13: D1605 Transformer

    EMI Filter are mounted on the skirt behind the 120 V AC Input Connector. ©1997 Radionics 74-07649-000-B 01/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Installation Page 13 of 17 1800 Abbott Street, Salinas, CA 93901, USA www.PDF-Zoo.com...
  • Page 14: Standby Batteries Installation

    Battery lead connections are not power limited. D.3.a. Standby Battery Selection The D9024 and D10024 panels supervise and charge the two 12 V sealed lead-acid batteries that are the standby power source. Several batteries are available from Radionics, and battery selection will depend on system design.
  • Page 15: D.3.B. Battery Wiring Connections

    Total Ah x 1.1 = Total Ah Requirements Maximum battery size permitted to be connected to the D9024 or D10024 is 38 Ah. Place the batteries in the enclosure as shown in Figure 14, D.3.b. Battery Wiring Connections The D10024 Literature Package contains a gray wire. Use this wire to connect the positive terminal of battery No.
  • Page 16: Figure 15: Front Panel Display

    ZONE/AREA DISPLAY LED DISPLAY Figure 15: Front Panel Display ©1997 Radionics 74-07649-000-B 01/97 All rights reserved ™The Radionics logo is a registered trademark of Radionics, D9024/D10024 Installation Page 16 of 17 1800 Abbott Street, Salinas, CA 93901, USA www.PDF-Zoo.com firealarmresources.com...
  • Page 17: Normal Operation

    To resound the alarms, press the Alarm Silence key. Press the System Reset key. For Assistance Contact: A copy of these instructions shall be framed and placed adjacent to the D9024 or D10024 control unit. ©1997 Radionics...

This manual is also suitable for:

D10024