D8024, D9024, D10024 Analog Fire Alarm Control Panels
Networking Guide
34377C 06/99
© 1999 Radionics, a division of Detection Systems, Inc.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D8024 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Radionics D8024

  • Page 1 D8024, D9024, D10024 Analog Fire Alarm Control Panels Networking Guide 34377C 06/99 © 1999 Radionics, a division of Detection Systems, Inc.
  • Page 2: Table Of Contents

    Figure 17: Commission Menu Three ..........................8 Figure 18: Network Menu One ............................9 Figure 19: Network Menu Two ............................9 Figure 20: Network Menu Four ............................9 D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 1 © 1999 Radionics. All rights reserved.
  • Page 3 Figure 60: Master/Slave Network..........................17 Figure 61: RS-485 High Integrity Network ........................17 Tables Table 1: Shared Zone Configuration ..........................5 Table 2: Panel Programming Options .......................... 16 D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 2 34377C 06/99...
  • Page 4: Notice

    These instructions are for connecting, programming, and operating D8024, D9024 and D10024 Fire Alarm Control Panels (FACP) in a network controlled by a D8024, D9024 or D10024 master panel. See the D8024 Installation Guide (P/N: 38728) and the D8024 Operator’s Guide (P/N: 35394), or the D9024, D10024 Installation Guide (P/N: 74-07649-000) and the D9024, D10024 Operator’s Guide (P/N: 74-07661-000) for specific information on...
  • Page 5: Network Installation

    • All panels must be D8024, D9024 or D10024 Fire Alarm Control Panels. The network wiring is supervised. A fault in the network wiring results in a warning message. In a fault condition on the network wiring each panel will operate as a stand-alone unit.
  • Page 6: Shared Zone Network

    This configuration can have up to 99 zones with 2,520 addressable points. See Table 1. • In the Shared Zone Network, up to four D8024, D9024 and/or D10024 panels are networked together with one panel designated to act as the Master.
  • Page 7: In A Fault Condition

    Shared Zone Network,” of this guide to program the slave panels. 6.2.1 Master Panel Programming, Shared Zone Network • Press the [>] key to display the Operator’s Menu, Main Level. Figure 4: Main Menu D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 6 34377C 06/99...
  • Page 8: Figure 5: Path Through Commission Menus To Network

    Press [Yes] if the master panel is not connected to a modem. If a modem is connected to Port B or Port C of the master panel, press [Change] to alter the statement to True and press [Enter]. The panel displays Network Menu Five. Figure 10: Network Menu Five D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 7 © 1999 Radionics. All rights reserved.
  • Page 9: Slave Panel Programming, Shared Zone Network

    Press [Yes] twice to reach Commission Menu Three (on CPU1). The panel displays Commission Menu Three. 1) Day Modes 2) Setup options 3) Network [10] 4) Devices 5) Talk to Slave Figure 17: Commission Menu Three D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 8 34377C 06/99...
  • Page 10: Figure 18: Network Menu One

    3) Network [10] 4) Devices 5) Talk to Slave Figure 25: Commission Menu Three • Press [No] to return to the Configure Menu. Figure 26: Configure Menu D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 9 © 1999 Radionics. All rights reserved.
  • Page 11: Report And Control Network

    The Report and Control Network links the individual panels to a master panel for reporting and control. Up to ten D8024, D9024 and/or D10024 panels may be networked together in a Report and Control Network with one dedicated panel designated to act as the Master.
  • Page 12: Fault Condition

    The displays on these devices mimic the text information on the LCD of the panel to which they are connected. The maximum number of outputs (notification appliances/relays) is 100 per panel. D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 11...
  • Page 13: Report And Control Network Programming

    Avoid confusion between network addresses and panel identifications by giving the master panel a unique identification number (i.e. 10). The panel displays Network Menu Two. Figure 35: Network Menu Two D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 12...
  • Page 14: Figure 36 Network Menu Three

    If necessary, use the [Change] key to select Global and press [Yes]. The panel displays Commission Menu Three. 1) Day Modes 2) Setup options 3) Network [10] 4) Devices 5) Talk to Slave Figure 43: Commission Menu Three D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 13 © 1999 Radionics. All rights reserved.
  • Page 15: Slave Panel Programming, Report And Control Network

    Enter a number and press [Enter]. The panel displays Network Menu Two. Figure 48: Network Menu Two • Press [0] and press [Enter]. The panel displays Network Menu Four. Figure 49: Network Menu Four D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 14 34377C 06/99...
  • Page 16: Figure 50: Network Menu Five

    Repeat the network programming procedure (see p.8, “6.2.2 Slave Panel Programming, Shared Zone Network”) for each slave panel. After completing network programming for the last slave panel press [No] from Commission Menu Three and return to Commission Menu Three for the Master Panel. D8024, D9024, D10024 Networking Guide 34377C 06/99 Page 15...
  • Page 17: 8.0 Panel Programming Options

    **The D9063 8-Input Module will be available in a future release. ***The D9075 RS-232/RS-485 Converter will be available in a future release. Figure 59: Mini Network D8024, D9024, D10024 Networking Guide © 1999 Radionics. All rights reserved. Page 16 34377C 06/99...
  • Page 18: Master/Slave

    • A dedicated Master (MCU) can control up to ten slave D8024, D9024 or D10024 FACPs. • Each slave D8024, D9024 and D10024 slave FACPs can be configured with a maximum number of D9067 Polling Circuit Modules. • A Master panel can also function as a fire panel by installing polling circuit modules.