DIP Switch Setting
(for service purposes only)
SMT/SI
Actuators for modulating control AME 110 NL, AME 120 NL
under the removable cover.
U/I - Input signal type selector
selected. If set to ON position, current input is
selected.
0/2 - Input signal range selector
the range from 2-10 V (voltage input) or from
4-20 mA (current input). If set to ON position,
the input signal is in the range from 0-10
V (voltage input) or from 0-20 mA (current
input).
D/I - Direct or inverse acting selector
acting (stem contracts as voltage increases). If
the actuator is set to ON position, the actuator
is inverse acting (stem extracts as voltage
increases).
---/Seq - Normal or sequential mode
selector
in the range 0(2)-10 V or 0(4)-20 mA. If set
(0(4-0(12) mA) or (5(6)-10 V) or
(10(12)-20 mA).
ON
Remark:
Factory setting: All switches (except switch 2 which is in ON position) are in OFF positions.
VD.KH.C6.02 © Danfoss 01/2014
0-5/5-10 V - Input signal range in
sequential mode
0(4)-10(12) mA. If set to ON position, the
5(6)-10 V or 10(12)-20 mA.
LIN/LOG - Linear or equal percentage flow
through valve selector
If set to ON position, the flow through the
position is linear acc. to the control signal.
---/ASTK - Anti-blocking function
is switched on. The actuator opens and closes
the valve every 7 days.
disabled.
Reset switch and reset button on PCB
Changing this switch position will cause the
Note: Reset switch
and reset button on
have the same function. The reset
button function active ( press it for 2 sec. ).
Reset
-5(6) V or
reset