EnerSys PowerSafe Data Safe Operation & Maintenance Manual page 53

Flooded lead-acid batteries c, d, e, f and g
Table of Contents

Advertisement

www.enersys.com
K TABLE
TABLE 13.1
Initial Temperature
o
(
C)
16.7
17.2
17.8
18.3
18.9
19.4
20.0
20.6
21.1
21.7
22.2
22.8
23.4
23.9
24.5
25.0
25.6
26.1
26.7
27.2
27.8
28.3
28.9
29.4
30.0
30.6
31.1
31.6
32.2
32.8
33.4
Publication No. US-FL-IOM-002 January 2007 Page
Factor K
o
(
F)
62
1.098
63
1.092
64
1.086
65
1.080
66
1.072
67
1.064
68
1.056
69
1.048
70
1.040
71
1.034
72
1.029
73
1.023
74
1.017
75
1.011
76
1.006
77
1.000
78
0.994
79
0.987
80
0.980
81
0.976
82
0.972
83
0.968
84
0.964
85
0.960
86
0.956
87
0.952
88
0.948
89
0.944
90
0.940
91
0.938
92
0.936