Relay PadPuls M1 User Manual page 11

1-channel m-bus pulse converter for reed signals
Hide thumbs Also See for PadPuls M1:
Table of Contents

Advertisement

Water, Heat, Electricity
Multiplicator
is the pulse increment (multiplicator) of the connected meter. For each
registered pulse the device adds "multiplicator" to the counter.
numerator can take values between 0 (no counting) and 255, the
denominator between 1 and 255.
Unit
is the physical unit of the counter and of the pulse increment. All proper
units including variants with power of ten, from the DIN EN 13757-3 are
offered in the selection list. Examples: m3, kWh, MJ
Counter
is the accumulated counter. It has to be related to the unit mentioned
above. The 5 byte binary type counter can be programmed equal to the
counter of the connected meter in a range of 0 to 1x10
1.099.511.627.775 ( = 00 FF FF FF FF FF hex.).
State
shows the M-Bus state in hexadecimal notation.
Write protection
is marked, if the device is protected against programming. Then you cannot
configure the adapter. The protection can be removed after opening the
sealable front cover of the housing and pressing the "Unprotect" pushbutton.
Permanent Error is not used for the PadPuls M1.
Write protect
transmits a command to the PadPuls M1 to activate write protection. The
PadPuls then allows no further configuration. It is protected against
unnoticed manipulation.
Read
reads the M-Bus device and refreshes the data on the selected sheet.
Write
sends the current options to the pulse converter, which stores this data into
the battery buffered memory. The PadPuls M1 changes the options only if
the write protection is deactivated. It is recommended to read and check the
data after writing.