2.2 Mounting The PW100 housing is mounted on a TS35 top-hat rail. The width of the housing is 6 horizontal pitches (6 HP) on the rail and, due to the low height of 60 mm, not only fits into a control cabinet, but also in a meter cabinet under the covers.
You can find all other patterns in the online help of the DS Manager (F1-button) in the chapter “Firmware Manuals / Device Server Application Firmware / Status LED Signals (Red = Green / Green = Yellow). PW100 · User Manual Version 1.0 - 11/2020...
DDC or a PC to read the connected meters by use of an M-Bus software (not in scope of delivery). The PW100 can also be used as a Repeater for extension of M-Bus networks relating to the cable length and number of meters.
3.4 Repeater Interface The PW100 can be used as a so-called Repeater, as a network extension for existing M-Bus systems, if the maximum number of meters or the maximum cable length has been exceeded for the installation. Up to 100 devices and up to 4km cable (1 x 2 x 0.8 JYSTY) at 2400 baud transmission speed can be connected to a...
3.5 USB interface The USB device port of the PW100 is as a USB 2.0 connector type B available on the front of the housing. Please use a USB cable with a type A plug on one end and a type B plug on the other side (not supplied) to connect a PC.
PCs in that network. This requires the so-called “Tibbo Device Server Toolkit” to be installed on that PC. With this software the Ethernet interface is configured in the PW100 and a virtual COM port is set up.
(32-Bit Windows) or tdst_5-09-12-x64.exe (64-Bit Windows) TDST = Tibbo Device Server Toolkit, 5-09-12 = Version 5.09.12 dated August 2014) After a reboot of the PC the installation of the drivers and software tools is completed. PW100 · User Manual Version 1.0 - 11/2020...
Please select the device which you want to configure and click on the button “Settings”. Then you see the settings of the device which you shall change according to the following pictures. You can get help for the DS Manager with F1 key. PW100 · User Manual Version 1.0 - 11/2020...
Page 12
PW100 Recommended settings: Change values marked with an arrow Stores settings and restarts the device PW100 · User Manual Version 1.0 - 11/2020...
You also don´t need a virtual port in the bridge mode (two device servers connected together, i.e. one TCP001 (serial device server) to the PW100. Please start the Tibbo – DS Manager (Start – Programs – Tibbo – Tibbo Device Server Toolkit –...
Page 14
DS manager respectively the VSP manager at any time. You can also change the settings of the device server and check its routing state after first setup using a web browser connected to the assigned IP address. The required password for the login is empty on delivery. PW100 · User Manual Version 1.0 - 11/2020...
3 pairs screw terminals for M-Bus, 3-pin screw terminal for each RS232C, 3-pin screw terminals for RS485, one pair screw terminals for Repeater, 3-pin screw terminals for power supply / protective ground PW100 · User Manual Version 1.0 - 11/2020...
USB cable A to B plug/plug, length = 1m, grey KA PATCH.5E RJ45 1M Network patch cable CAT5E FTP, Length = 1m, grey KA006 Serial D-SUB-9 female cable with 3 open wires PW100 · User Manual Version 1.0 - 11/2020...