SCC4 INSTAllATION ANd OpeRATION SCCX6 Extension INSTRuCTIONS MulTI-BOIleR MOdulATING heATING CONTROl fOR hydRONIC heATING SySTeMS SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 115VAC 60Hz , 12VA MAX USE COPPER CONDUCTORS ONLY ENCLOSED CAUTION : RISK OF ELECTRIC SHOCK...
SCC4 and SCCX6-Extension Installation Manual SCC4 OveRvIeW SequeNCeS up TO 4 fully MOdulATING STAGeS. The SCC4 is the perfect control whenever multiple fully modulating stages are required for hydronic heating applications. The SCC4 controls the on/off and the modulation of each stage to maintain precise system set point control. pId Type lOGIC The SCC4’s control algorithms allow it to look at the rate of change in the system.
Triangle Tube Optima Series SCC4 lAyOuT Program Switch to restrict access to The digital display shows the system status, set point, function changes. This switch is lead stage <in brackets>, and status of each stage. covered with Wiring Enclosure. To view and adjust settings, press the appropriate buttons.
SCC4 and SCCX6-Extension Installation Manual SCCX6 eXTeNSION lAyOuT Extension Selection Switch to determine Stage letters and LED colors. Ext-A Stages E - J and all LEDs are Green Ext-B Stages K - P and all LEDs are Red LED indicates the This switch is covered with the Wiring Enclosure. associated relay status.
Triangle Tube Optima Series uNdeRSTANdING OpeRATION CONCepT 1:1.5 The SCC4 has multiple operating modes that satisfy most hydronic systems. It can change the 1:1.25 System Set Point based on outdoor temperature (Outdoor Reset) or it can modulate its stages to achieve an adjustable fixed Set Point.
SCC4 and SCCX6-Extension Installation Manual MAke SuRe yOu hAve The RIGhT CONTROl If you need the SCC4 to do additional tasks that either are not listed or do not know how to configure them, contact Triangle Tube Engineering Department by Phone (856) 228-8881 or Fax (856) 228-3584. INITIAl SeTup Setting an Initial Program will ease the configuration of the SCC4 and will give the opportunity to utilize many of the energy saving features and give more comfortable heat when needed.
Triangle Tube Optima Series SeTBACk OR dAy/NIGhT SChedulING Two Setback modes are available for the SCC4: • The Day/Night Scheduling provides an adjustable time-based schedule for the Setback. • The Setback mode uses an external signal to switch the operation of the SCC4 in and out of setback mode.
SCC4 and SCCX6-Extension Installation Manual INSTAll The SeNSORS Immersion Heating System Sensor Immersion Well Common Supply Pipe 3/8" ID 1/2" NPT heATING SySTeM SeNSOR (hSS) INSTAllATION heATING SySTeM SeNSOR hSS Shield • Put the Heating System sensor approximately 10' feet past the last boiler on the common supply header but before any major takeoffs.
Triangle Tube Optima Series WIRING The SeNSORS Mini-MOD WARNING Full Modulation Sequencing Control SYSTEM Connect the shield at the control terminal end and cut the shield wire at the sensor end. OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL...
SCC4 and SCCX6-Extension Installation Manual WIRING The dOMeSTIC hOT WATeR CAll dhW (TeRMINAlS 29, 30) • DHW can be used to raise system Set Point to the DHW Set Point. DHW with or without Priority must be selected in the Startup Menu. See "Prove/Domestic Hot Water (DHW) Priority" on page 16 •...
Triangle Tube Optima Series MeNu SequeNCe ----------- SETTINGS ------------ ------------- SEASON -------------- ------- OUTDOOR CUTOFF ------- Season Winter Winter Set Point 120 F Summer <System Settings> <Maintenance> BACK SAVE <Histories> BACK SAVE <System Startup> ------------ SET POINT ---------- BACK SELECT Reset Ratio...
Page 13
SCC4 and SCCX6-Extension Installation Manual ---------------- GAIN -------------- ----------- SETTINGS ------------ Season Winter Set Point 120 F <System Settings> SYSTEM SETTINGS1 <Maintenance> <Histories> BACK SAVE ---------- SETTINGS 1 ---------- <System Startup> Gain BACK SELECT Lead Rotation Time -------- LEAD ROTATION ------- Purge Delay 2.0min Manual Lag Delay 0min...
LISTED More than one disconnect switch may be required 99RA to de-energize the equipment before servicing. Triangle Tube Optima Series DO NOT APPLY AN PROGRAM TO INPUT TER WIRING The vOlTAGe MOdulATING MOTORS (A TeRMINAlS 13, 15), (B TeRMINAlS 16, 18),...
USE COPPER CONDUCTORS ONLY STARTUP ----------- SETTINGS ------------ ------------- SEASON -------------- STARTUP Season Winter Winter Set Point SCC4 and SCCX6-Extension Installation Manual 120 F Summer -------- SYSTEM STARTUP ------ -------- SYSTEM STARTUP ------ <System Settings> <Maintenance> BACK SAVE AleRT STARTup SeTTINGS (START) ----------- SETTINGS ------------ ------------- SEASON -------------- (START) ENCLOSED...
BACK SAVE ------------ SET POINT ---------- THESE SETTINGS BACK SELECT Enabled CHANGE PRIMARY ------------- WARNING ------------ Triangle Tube Optima Series ------ EMS INPUT MODE ------- SYSTEM FUNCTIONS. ------ EMS 20ma SETPOINT----- Disable THESE SETTINGS BACK CONTINUE Enable CHANGE PRIMARY steel and cast iron boilers or boilers with low turndown ratios.
------ MODULATION MODE ------ ----- PROVE/DHW SHARING ---- Normal ------- DHW SETPOINT ------- SCC4 and SCCX6-Extension Installation Manual Prove Parallel DHW Priority DHW No Priority 30 minutes before the start of the Day schedule setting. That is, if the normal day set point at a specific outdoor was 145˚F and the BACK SAVE No Priority (Summer)
Triangle Tube Optima Series ENCLOSED ENERGY CAUTION : RISK OF ELECTRIC SHOCK MANAGEMENT More than one disconnect switch may be required EQUIPMENT OpeRATING SeTTINGS to de-energize the equipment before servicing. 99RA pROGRAM ChANGe SeTTINGS PROGRAM To be able to change the SCC4 settings, the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security.
Set Point 120 F Summer <System Settings> <Maintenance> BACK SAVE <Histories> SCC4 and SCCX6-Extension Installation Manual <System Startup> ------------ SET POINT ---------- BACK SELECT OuTdOOR CuTOff TeMpeRATuRe ----------- SETTINGS ------------ ------------- SEASON -------------- ------- OUTDOOR CUTOFF ------- Adjustable Off, from 20ºF/-7ºC to 100ºF/38ºC, On Season Winter Winter Default: 64ºF/ 18ºC Set Point 120 F Summer Button: MENU/Set Point/Outdoor Cutoff...
Set Point 120 F <System Settings> SYSTEM SETTINGS1 <Maintenance> Triangle Tube Optima Series <Histories> ---------- SETTINGS 1 ---------- <System Startup> Gain ----------- SETTINGS ------------ BACK SELECT Lead Rotation Time Season Winter Purge Delay 2.0min Set Point 120 F Lag Delay 0min <System Settings>...
SYSTEM SETTINGS2 Outdoor Trim +0 F ------- SOFT-OFF DELAY -------- Set Time 12:03Pm Lag Delay 0min Soft-Off Delay 45sec <Day/Night Schedules> <More Settings> <Output Trim> BACK SELECT BACK SELECT <Configuration> ---------- SETTINGS 2 ---------- SCC4 and SCCX6-Extension Installation Manual MAINTENANCE BACK SELECT Standby Time 10min BACK SAVE...
BACK SAVE Day Schedule **:** Night Schedule **:** -- OUTDOOR SENSOR TRIM ---- ---------- MAINTENANCE --------- --- AUTO ROTATE PERIOD --- Triangle Tube Optima Series System Trim +0 F SYSTEM SETTINGS2 Outdoor Trim +0 F BACK SELECT Soft-Off Delay 45sec <Output Trim>...
Day Schedule **:** Setback 10 F Night Schedule **:** -- OUTDOOR SENSOR TRIM ---- Last Stage Hold ------- SOFT-OFF DELAY -------- Set Time 12:03Pm <Day/Night Schedules> SCC4 and SCCX6-Extension Installation Manual BACK SELECT BACK SELECT BACK SAVE -------------- SETBACK ----------- dAy/NIGhT SCheduleS --- DAY/NIGHT SCHEDULES --- BACK SAVE BACK...
120 F <Configuration> INPUT RATINGS: <System Settings> BACK SELECT BACK SELECT <Maintenance> 115VAC 60Hz , 12VA MAX Triangle Tube Optima Series <Histories> USE COPPER CONDUCTORS ONLY MAINTENANCE <System Startup> ------- SOFT-OFF DELAY -------- BACK SELECT MAINTeNANCe MAINTENANCE ---------- MAINTENANCE --------- System Trim +0 F Button: MENU/<Maintenance>...
SCC4 and SCCX6-Extension Installation Manual BACK SAVE BACK SAVE CONfIGuRATION ------ CONFIGURATION 1 ------ ------ CONFIGURATION 1 ------ Button: MENU/<Maintenance>/<Configuration> v1.00c v1.00c • This menu option provides a consolidated view of the SCC4's Startup and Stage settings. Reset F Reset F Parallel Parallel Shutdown/Disable Shutdown/Disable All On dISplAy...
STAGE MENU Triangle Tube Optima Series BOIleR STAGe SeTTINGS ----- STAGE A SETTINGS ---- Button: STAGE/ Mode Ignition % The Stage menu offers the capability of adjusting each of the boiler's operation individually. Mode Start % <Prev Stage> • In most installations, all active boiler adjustments are the same, but each can be configured <Next Stage>...
SCC4 and SCCX6-Extension Installation Manual STAGE MENU BACK SAVE MOdulATION START % ------------ STAGE A ------------ Adjustable from 0% to 100% Default: 40% MODULATION START Button: STAGE/Mod Start % • The Modulation Start determines at what modulation percent the previous boiler should be ----- STAGE A SETTINGS ---- for the current boiler to be activated. Mode Ignition % •...
Triangle Tube Optima Series TROuBleShOOTING SeNSOR INpuTS display shows Sensor OpeN or ShORT When OPEN, Check the sensor is connected and the wires are continuous to the SCC4. Finally follow the procedure for Incorrect Temperature Display. When SHORT Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the SCC4 may be damaged.
SCC4 and SCCX6-Extension Installation Manual MulTIple MOdulATING BOIleRS dIReCT heATING pIpING dIAGRAM Outdoor Sensor SYSTEM SCC4 PROGRAM 120VAC Boiler 1 Boiler 2 Boiler 3 Boiler 4 System Sensor Building Heating Loop System: The SCC4 controls 4 modulating boilers The boilers are piped in Reverse Return on the primary loop The System output is controlling the System Pump Triangle Tube is aware that each installation is unique Thus, Triangle Tube is not responsible for any installation related to any electrical or plumbing diagram generated by Triangle Tube The provided illustrations are to demonstrate Triangle Tube’s control operating concept only...
Triangle Tube Optima Series MulTIple MOdulATING BOIleRS dIReCT heATING WIRING dIAGRAM SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS 4-20mA Modulating INPUT RATINGS: 115VAC 60Hz , 30VA MAX USE COPPER WIRE, CLASS 1 WIRE ONLY.
SCC4 and SCCX6-Extension Installation Manual SCC4 WIRING TO 4 pReSTIGe BOIleRS SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 115VAC 60Hz , 30VA MAX USE COPPER WIRE, CLASS 1 WIRE ONLY. SCC4 120 VAC CAUTION : RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.