To handle the service cap
Take the following guidelines into account:
▪ Always  use  a  charge  hose  equipped  with  a  valve  depressor  pin,
since the service port is a Schrader type valve.
▪ After  handling  the  service  port,  tighten  the  service  port  cap
securely.  For  the  tightening  torque,  refer  to  the  table  in  chapter
"To handle the stem cap" on page 12.
▪ Check for refrigerant leaks after tightening the service port cap.
6.4.8
To connect the refrigerant piping to the
outdoor unit
1 Do the following:
▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).
a
b
c
d
2 Choose a piping route (a, b, c or d).
d
a
c
b
3 If you have chosen the downwards piping route:
▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.
a
b
4× Ø6 mm
c
c
4 Do the following:
▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.
b
a
5 Do the following:
▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Wind  heat  insulation  around  the  curves,  and  then  cover  it
with vinyl tape (c).
▪ Make  sure  the  field  piping  does  not  touch  any  compressor
components (d).
▪ Seal the insulation ends (sealant etc.) (e).
AZQS100~140B8V1B + AZQS100~140B7Y1B
Split system air conditioners
4P385529­1 – 2014.08
f
d
6 If  the  outdoor  unit  is  installed  above  the  indoor  unit,  cover  the
stop  valves  (f,  see  above)  with  sealing  material  to  prevent
condensed water on the stop valves from moving to the indoor
unit.
NOTICE
Any exposed piping might cause condensation.
7 Reattach the service cover and the piping intake plate.
8 Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.
a
WARNING
Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After  making  the  knockout  holes,  we  recommend  you
remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.
▪ When  passing  electrical  wiring  through  the  knockout
holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.
a
b
a
Knockout hole
b
Burr
c
Sealant etc.
NOTICE
Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.
6 Installation
e
a
b
c
c
Installer reference guide
13