EMS 5000 FIREPOINT

6.2 VHF Remote Receiver

The VHF remote receiver 53-5414 should be wired as shown in the supplied drawing
P03077. The following paragraphs outline the installation in a step by step format.
Remove the four lid retaining screws situated on the front cover. The front section of the
unit can now be removed.
Four fixing holes are available for the unit's installation. These are clearly on the outside
of the casing.
Offer the back box up to the wall and check that the rear tamper switch operates.
Should the microswitch not operate, remove the unit from the wall and carefully adjust
the microswitch arm. Once the microswitch operates correctly the unit can be fixed to
the wall and all external wiring connections made.
The diagram P03077 shows the wiring connections required for the remote receiver.
Only those cables needed to make the remote receiver function should be routed into
the case. The Remote Receiver must NOT be used as a junction box or cable termination
point as this will adversely affect the performance of the system.
When all connections have been made to the remote receiver the battery can be
connected, the lid can be re-fixed and mains voltage can then be applied.