4.2.2 Configuration Registers
Register Address
(protocol address)
13
14
15
21
45
48
49
50
81
99
While the initialization is ongoing, some Modbus registers will indicate an undetermined value.
Once the normal operation starts, they will acquire its corresponding value. It is important to
keep in mind that any change done during the initialization process will not have effect until it
has been finished.
11
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SLU
MH-RC-MBS-1
Register Address
(PLC address)
14
15
16
22
46
49
50
51
82
100
R/W
Description
"Open Window" switch-off timeout
R/W
0..30 (minutes)
▪
Factory setting: 30 (minutes)
▪
Modbus RTU baud-rate
2400bps
▪
4800bps
▪
9600bps (Default)
▪
R
19200bps
▪
38400bps
▪
57600bps
▪
76800bps
▪
115200bps
▪
Modbus Slave Address
R
1..63
▪
R
Max number of fan speeds
Error reset
W
1: Reset
▪
R
Switch value
R
Device ID: 0x0F00
R
Software version
Error address
R
Provides the indoor unit number which is
▪
providing error
Reset
W
1: Reset
▪