Modbus rtu eia-485 interface for daikin air conditioners. compatible with vrv and sky line air conditioners commercialized by daikin (23 pages)
Summary of Contents for IntesisBox ME-AC-MBS-1
Page 1
IntesisBox ® ME-AC-MBS-1 v.2.1 Modbus (EIA-485) Interface Mitsubishi Electric conditioners. Compatible with all models of Domestic & Mr.Slim lines. User Manual Issue Date: 11/2017 r21 EN Order Codes: ME-AC-MBS-1: Modbus RTU Interface for Mitsubishi Electric air conditioners...
ME-AC-MBS-1 User’s Manual r21 EN INDEX Presentation ......................4 Connection ......................5 Connect to the AC indoor unit ................5 Connection to the EIA-485 bus ................5 Quick Start Guide ....................6 Modbus Interface Specification ................7 Modbus physical layer..................7 Modbus Registers ....................
CN105 of the AC unit's electronic circuit. You can place the ME-AC-MBS-1 inside or outside the AC indoor unit depending on your needs. Remember that the ME-AC-MBS-1 must also be connected to the Modbus RTU EIA-485 network.
4. Connect the EIA-485 bus to the interface’s EIA485 connector. 5. Close the AC indoor unit. 6. Check the DIP-Switch configuration of the IntesisBox interface and make sure it matches the current installation’s parameters (see section 4.3). By default, the interface is set to: Modbus Slave Address ...
4. Modbus Interface Specification 4.1 Modbus physical layer ME-AC-MBS-1 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps).
Page 8
65535 (-1 if it is read as signed value): ▪ Status of AC error has not been obtained yet (initialization value). Error in the communication of ME-AC-MBS-1 with the AC unit. Any other error present, see the table at the ▪...
This register allows us to provide an external temperature’s sensor from the Modbus side. Mitsubishi indoor unit does not allow, on devices like ME-AC-MBS-1, to provide directly a temperature to be used as a reference of the control loop of the AC indoor unit.
Page 11
As it has been detailed on the previous point, the real temperature setpoint in the indoor unit and the temperature setpoint requested from ME-AC-MBS-1 might differ (when a value in register 22/23 – “external temperature reference” is entered). This register always informs about the current temperature setpoint which is being used by the indoor unit –...
User’s Manual r21 EN 4.3 DIP-switch Configuration Interface All the configuration values on ME-AC-MBS-1 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface. The device has DIP-switches SW1, SW3 and SW4 on the following locations:...
This mechanism must be supplied by the Modbus master. The ME-AC-MBS-1 device includes an on-board terminator resistor of 120Ω that can be connected to the EIA-485 bus by using DIP-switch SW4. Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor and/or fail-safe biasing mechanism (check the technical documentation of the Master device connected to the EIA-485 network in each case).
ME-AC-MBS-1 User’s Manual r21 EN 5. Electrical and Mechanical features Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): Operation Enclosure 0ºC to +60ºC 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Temperature Color: Light Grey. RAL 7035...
ME-AC-MBS-1 User’s Manual r21 EN 7. Error Codes Error Code Description No active error 1102 Discharge Temperature high 1108 Internal thermostat detector working (49C) 1110 Outdoor unit fail 1300 Pressure low 1302 Pressure high (High pressure probe working 63H) 1503...
Need help?
Do you have a question about the ME-AC-MBS-1 and is the answer not in the manual?
Questions and answers