AHU COMMUNICATIONS KIT INSTALLATION
RS485 Communication Port
Name
Port
MULTI V IDU
RS485 CH2
Comm.
Single IDU
SINGLE N/SIG
Comm.
NTC Thermistor
Name
Port
Thermistor
NTC RI2/G
Discharge
ThermistorPipein
NTC RI3/G
Thermistor Pipe
NTC RI4/G
out
Remote Controller
Name
Port
REMO
+12V/SIG/GND
Electronic Expansion Valve
Name
Port
EEV
12 VDC/1/2/3/4
Note :
When a communication module(or PAHCMR000) is connected to the main module of PAHCMS000, DO and UI in communication
module are not used.
Item
MULTI V Comm.
(IDU A/B)
Single split Comm.
(IDU A/B)
Item
Discharge air Thermistor
Pipe in (Liquid) Thermistor
Pipe out(Gas)Thermistor
Item
Electrical Spec.
Wire Remote
Max 164 ft
Controller
Item
Electrical Spec.
EEV Control
Max 32.8 ft
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

Communication Module

Electrical Spec.
Max 3280 ft,
Communication with MULTI V
2C x 18~16 AWG
Outdoor unit
(shield wire)
Max 246 ft,
Communication with Single Split
2C x 18~16 AWG
Outdoor unit
(shield wire)
Electrical Spec.
NTC 10 kΩ, 16.4 ft
Discharge Air temperature sensor
NTC 5 kΩ, 16.4 ft
Inlet pipe (Liquid) Temp. sensor
NTC 5 kΩ, 16.4 ft
Outlet pipe (Gas) Temp. sensor
Communication with Wired Remote Controller
EEV Control
Function
Function
Function
Function