Appendix; List Of Important Alarms And Faults; A.1 List Of Important Alarms And Faults - Siemens Sinamics S120 Getting Started

Starter
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Appendix

A.1

List of important alarms and faults

Axxxxx: Alarm
Fyyyyy: Fault
Table A- 1
The most important alarms and faults
Number
Cause
F07085
Control parameters were compulsorily changed for
the following reasons:
They exceeded dynamic limits due to different
parameters.
They are not applicable because of properties of
the detected hardware that are not present.
The value is estimated as the thermal time con-
stant is missing.
Motor temperature model 1 is activated as thermal
motor protection is missing.
F07802
Infeed or drive does not reply a 'ready' after an inter-
nal actuation command.
Monitoring time too short.
DC link voltage not available.
Associated infeed or drive of the reporting compo-
nents defective.
Supply voltage incorrectly set.
Getting Started with STARTER
Getting Started, 11/2017, 6SL3097-4AG00-0BP5
Remedy
Not necessary.
No parameter change is necessary as the parameters
have already been limited to a reasonable level.
Extend monitoring time (p0857).
Ensure the DC link voltage. Check the DC link
voltage. Enable the infeed.
Replace associated infeed or drive of the reporting
components.
Check settings of the supply voltage (p0210).